Bryant 582A User Manual
Page 3
Fig. 2—582A018-042 and 583A024-036 Unit Dimensions
UNIT
ELECTRICAL CHARACTERISTICS
UNIT WEIGHT
UNIT HEIGHT IN. (MM)
″
A
″
CENTER OF GRAVITY
IN. (MM)
lb
kg
X
Y
Z
582A018040
208/230-1-60
249.0
113.2
35.02 (889.5)
20.0 (508.0)
14.0 (355.6)
15.0 (381.0)
582A024040/060
208/230-1-60
280.0
127.3
35.02 (889.5)
22.5 (571.5)
13.0 (330.2)
15.0 (381.0)
582A030040/060
208/230-1-60, 208/230-3-60
280.0
127.3
35.02 (889.5)
21.5 (546.1)
13.75 (349.3)
15.0 (381.0)
582A036060/090
208/230-1-60, 208/230-3-60, 460-3-60
320.0
145.1
37.02 (940.3)
22.5 (571.5)
14.0 (355.6)
13.0 (330.2)
582A042060/090
208/230-1-60, 208/230-3-60, 460-3-60
355.0
161.4
35.02 (889.5)
21.5 (546.1)
13.5 (342.9)
13.0 (330.2)
583A024040/060
208/230-1-60
290.0
131.5
37.02 (940.3)
22.0 (558.8)
14.5 (368.3)
16.0 (406.4)
583A030040/060
208/230-1-60, 208/230-3-60
313.0
142.0
39.02 (991.1)
22.0 (558.8)
15.3 (387.4)
17.6 (447.0)
583A036060/090
208/230-1-60, 208/230-3-60, 460-3-60
321.0
145.6
35.02 (889.5)
22.0 (558.8)
15.3 (387.4)
16.5 (419.1)
C00055
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
INCHES [mm]
EVAP. COIL ACCESS SIDE............................................................36.00 [914.0]
POWER ENTRY SIDE....................................................................36.00 [914.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP .......................................................................................48.00 [1219.2]
SIDE OPPOSITE DUCTS ..............................................................36.00 [914.0]
DUCT PANEL .................................................................................12.00 [304.8] *
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
INCHES [mm]
TOP OF UNIT...................................................................................14.00 [355.6]
DUCT SIDE OF UNIT.........................................................................2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]
BOTTOM OF UNIT .............................................................................0.50 [12.7]
ELECTRIC HEAT PANEL .................................................................36.00 [914.4]
NEC. REQUIRED CLEARANCES.
INCHES [mm]
BETWEEN UNITS, POWER ENTRY SIDE ....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]
LEGEND
CG - Center of Gravity
COND - Condensor
EVAP - Evaporator
NEC - National Electrical Code
REQ’D - Required
NOTE: Dimensions are in in. [mm]
—3—