Page 47

background image

3. Check to be sure tools, loose parts, and debris are removed

from the unit.

4. Check to be sure all panels and screws are in place and

tight.

Desert and Seacoast Locations

Special consideration must be given to the installation and main-
tenance of condensing units and heat pumps installed in seacoast
or desert locations. Salt and the alkali content of the sand adhere
to the aluminum fins of the coil and can cause premature coil
failure due to corrosion.

Preventive measures can be taken during installations, such as:

1. Locating the unit on side of structure opposite the prevailing

winds.

2. Elevating the unit to height where drifting sand cannot pile

up against coil. Four-in.-high mounting feet or an 18-in.-
high mounting rack are available as accessories and can be
used to elevate the unit.

3. Addition of coastal filter (see pre-sale literature for acces-

sory listing).

Special maintenance requirements are as follows:

1. Frequent inspection of coil and base pan, especially after

storms and/or high winds.

2. Cleaning coil by flushing out sand from between coil fins

and out of base pan as frequently as inspection determines
necessary.

3. Protecting the unit in

off season

with cover that allows air

to circulate through but prevents sand from sifting in (such
as canvas material). Do not use plastic as plastic will hold
moisture.