beautypg.com

Bryant R-22 User Manual

Page 33

background image

AUXILIARY HEAT (W2) LOCKOUT
In some areas, it is necessary to disable the auxiliary heat, except
for defrost, until the outdoor ambient is less than the structure’s
balance point. This is accomplished by using the low-voltage
wiring as shown in Fig. 36. Wire the 24vac W2 signal from the
indoor thermostat to W3 of the control, and W2 of the control to
W2 of the indoor unit. When the outdoor ambient is less than the
setting of the balance-point POT, the 24vac signal energizes the
auxiliary heat (W2) of the indoor unit.
EMERGENCY HEAT
If the 2-speed control receives a call for auxiliary heat (W2)
without a heat-pump heating (Y1) call, the second auxiliary stage
(W3) is energized. This ensures all available heat is energized if
the indoor thermostat is switched to emergency heat.
COMPRESSOR PTC-OVERLOAD PROTECTION
The control senses the resistance of the compressor internal
positive-temperature coefficient (PTC) overloads. If the resistance
of the PTCs is out of range, the control shuts off the unit until the
resistance range is acceptable. See Table 16 for compressor PTC
ranges.

When the control turns off the outdoor unit due to out-of-range
PTCs, the unit remains off for 15 minutes with the outdoor fan
running. After 15 minutes, the control checks the resistance every
5 minutes until it reaches the reset range. During this time, a
malfunction signal appears on the control board. If this happens,
remove the wires on control board at S1 and S2 and measure the
resistance across the leads. When the resistance reaches 8,400 to
10,000 ohms, system operation may be resumed. If the resistance
remains outside this range, a quick check of the leads at the
compressor should be made. Loose connections can cause inaccu-
rate readings. If a PTC trip occurs 3 times, the control will lock out
the outdoor-unit operation and provide malfunction signals at both
the control and indoor thermostat.

PRESSURE SWITCH PROTECTION

The outdoor unit is equipped with high- and low-pressure
switches, wired in series. If a pressure switch opens, the control
provides a 5-minute time delay in outdoor unit operation with the
outdoor fan running. A malfunction signal appears on the control
when a pressure switch opens. If the switch remains open for 1 hr
or longer, a malfunction signal is provided at the L terminal of the
indoor thermostat.

III.

FACTORY DEFAULTS

Factory defaults have been provided in the event of failure of the
ambient thermistor, outdoor-coil thermistor, and/or furnace inter-
face jumper. Refer to Table 17 for default and function.

IV.

MAJOR COMPONENTS

TWO-SPEED CONTROL

The 2-speed control board controls the following functions:

High- and low-compressor contactor operation

Outdoor fan-motor operation

Crankcase-heater operation

Compressor protection

Pressure-switch monitoring

Second-stage latching

Time delays

5-minute time-delay speedup (bypass)

Heat pumps:

Time/temperature defrost

Defrost-interval selection

Furnace interface

Electric-heat staging

HEADER-PIN HOUSING

The header-pin housing is the plastic assembly which holds the
stripped-lead ends for field connections. The 2-speed control
receives the 24vac low-voltage control-system inputs through the
housing/pins. The housing also contains jumpers which the control
uses for system configuration, such as heat pump versus air
conditioner. See Fig. 37 for header-pin housing configurations.

TWO-SPEED COMPRESSOR

The 2-speed compressor contains motor windings that provide
low-speed, 4–pole (1750 rpm) and high-speed, 2–pole (3500 rpm)
operation. Refer to Fig. 38 to determine which windings are
energized at each speed. Refer to Compressor Winding-Check
section under Troubleshooting and Table 18 for appropriate
winding resistances.

The 2-speed compressor is also protected by an internal-pressure
relief (IPR), which relieves discharge gas into the compressor shell
(low side) when the differential between suction and discharge

TABLE 17—FACTORY DEFAULTS

FAILED COMPONENT

FUNCTION

DEFAULT

Ambient Thermistor

Crankcase Heater

Energized during any off cycle

Second-Stage Latching

Does not function

Furnace Interface

Balance point does not function, but

interface still energizes furnace and

locks out heat pump with a call for W2

Heating Switchover Speed Point

Unit only runs in high-

compressor speed

Defrost Initiation

Defrost is initiated based on coil

temperature only

Outdoor Thermostat for

Auxiliary Heat

Anytime there is a call for W2,

W3 is also energized.

Outdoor Coil Thermistor

Defrost Initiation and Termination

Defrost occurs at each time interval,

but terminates after 5 minutes

Furnace Interface Jumper

Furnace Interface

Does not function

Fig. 36—Low-Voltage Control Wiring

A93572

W2

W3

W3

W2

W2

TWO SPEED

THERMOSTAT

TWO SPEED

HEAT PUMP

FAN

COIL

CONTROL
LOGIC

TABLE 16—COMPRESSOR PTC RANGES

COMPRESSOR INTERNAL-PTC RESISTANCE

Safe Range (77°F)

1.5k to 7.8k ohms

To trip

26k to 34k ohms

To reset

8.4k to 10k ohms

—33—