6 Commissoning, operation
28
WIKA operating instructions digital indicator DI10
6.7 Default values
Reset to default values
To return the unit to a defined basic state, a reset can be carried out to the
default values. The indicator must be in “ULOC” mode. An accidental reset
during operation is avoided..
The following procedure should be used:
Switch off the power supply
Press
button
[P]
Switch on loop current (approx. 3.8 mA) and press [P]-button until
„- - - -“ is shown in the display.
With reset, the default values of the program table are loaded and used for
subsequent operation. This puts the unit back to the state in which it was
supplied.
Caution!
All application-related data are lost.