Mounting to control panel – WIKA CS4S User Manual
Page 8
Operating Instructions Temperature Indicating Controller CS4S
V1.1
•
10/2006
- 8 -
3. Mounting to control panel
3.1 Site selection
This instrument is intended to be used under the following environmental conditions (IEC61010-1):
Overvoltage category , Pollution degree 2
Mount the controller in a place with:
•
A minimum of dust, and an absence of corrosive gases
•
No flammable, explosive gasses
•
Few mechanical vibrations or shocks
•
No exposure to direct sunlight
•
An ambient temperature of 0 … 50 °C (32 … 122 °F), which does not change rapidly
•
An ambient non-condensing humidity of 35 … 85 %RH
• No large capacity electromagnetic switches or cables through which large current is flowing
• No water, oil or chemicals or where the vapors of these substances can come into direct contact with the
controller
3.2 External dimension
(Fig.
3.2-1)
3.3 Panel cutout
Lateral
close
mounting
n: Number of units mounted
Caution: If lateral close mounting is used for the
controller, IP66 specification will not be fulfilled.