beautypg.com

Mounting to control panel – WIKA CS4S User Manual

Page 8

background image

Operating Instructions Temperature Indicating Controller CS4S

V1.1

10/2006

- 8 -

3. Mounting to control panel

3.1 Site selection

This instrument is intended to be used under the following environmental conditions (IEC61010-1):

Overvoltage category , Pollution degree 2
Mount the controller in a place with:

A minimum of dust, and an absence of corrosive gases

No flammable, explosive gasses

Few mechanical vibrations or shocks

No exposure to direct sunlight

An ambient temperature of 0 … 50 °C (32 … 122 °F), which does not change rapidly

An ambient non-condensing humidity of 35 … 85 %RH

No large capacity electromagnetic switches or cables through which large current is flowing
No water, oil or chemicals or where the vapors of these substances can come into direct contact with the

controller

3.2 External dimension












(Fig.

3.2-1)


3.3 Panel cutout


Lateral

close

mounting

n: Number of units mounted


Caution: If lateral close mounting is used for the

controller, IP66 specification will not be fulfilled.



(Fig.

3.3-1)

75

45

+0.5

0

45

+0

.5 0

45

+0

.5 0

n x 48-3

+0.5

0

48

11.5

95

44.5

59

.7

Gasket

Screw type mounting bracket