Operating Instructions Temperature Indicating Controller CS4S

V1.1

10/2006

- 20 -

Energized/Deenergized

When [alarm action energized] is selected, the alarm output (between terminals 3-4, or 3-5) is conducted
(ON) while the alarm output indicator is lit.
The alarm output is not conducted (OFF) while the alarm output indicator is not lit.

When [alarm action deenergized] is selected, the alarm output (between terminals 3-4, or 3-5) is not
conducted (OFF) while the alarm output indicator is lit.
The alarm output is conducted (ON) while the alarm output indicator is not lit.

High limit alarm (when Energized is set) High limit alarm (when Deenergized is set)










(Fig. 5.5-1)

(Fig. 5.5-2)

5.6 Auto/Manual control function

Name,

Functions

Auto/Manual control function
• If Auto/Manual control function is selected in the

OUT

/

OFF

key function selection, Automatic or Manual

control function can be switched by pressing the

MODE key in the PV/SV display mode.

If control action is switched from automatic to manual or vice versa, balanceless-bumpless function
works to prevent sudden change of manipulated variable.
When automatic control is switched to manual control, the 1st dot from the right on the SV display
blinks, and the output manipulated variable (MV) can be increased or decreased by pressing

or

key to perform the control.
By pressing the

MODE key again, the mode reverts to the PV/SV display mode (automatic control).

(Whenever the power to the controller is turned on, automatic control starts.)

5.7 Control output OFF function

Character

Name,

Functions

Control output OFF function

• A function to pause the control action or turn the control output of the unused instrument

of the plural units OFF even if the power to the instrument is supplied.
[

] is indicated on the PV display while the function is working.

• Once the control output OFF function is enabled, the function cannot be released even

if the power to the instrument is turned OFF and ON again.
To cancel the function, press the

MODE key again for approx. 1 second.

5.8 Output manipulated variable (MV) indication

Name and functions

Output manipulated variable indication
In the PV/SV display mode, press the

MODE key for approx. 3 seconds.

Keep pressing the MODE key until the output manipulated variable shows up, though the main
setting mode appears temporarily during the process.
(The SV display indicates output manipulated variable and the decimal point blinks at a cycle of every
0.5 second). If the

MODE key is pressed again, the mode reverts to the PV/SV display.

OFF

ON

A1 hysteresis

SV setting

+ A1 set point

OFF

ON

SV setting

+ A1 set point

A1 hysteresis