Operating Instructions Temperature Indicating Controller CS4S
V1.1
•
10/2006
- 30 -
Attached functions
:
[Setting value lock], [Sensor correction], [Auto/manual control switching],
[Input burnout indication]
Thermocouple and RTD inputs
If the input value exceeds the Indication range high limit value, the PV display blinks “
”, and if
the input value exceeds the Indication range low limit value, the PV display blinks “
”.
If the input value exceeds the Control range, OUT1 and OUT2 are turned off (for Control output analogue
current signal: OUT1 low limit value and OUT2 low limit value).
(However, for manual control, it outputs the preset manipulated variable)
Input
Input range
Indication range
Control range
–199.9 ... 400.0 °C
–199.9 ... 450.0 °C
–205.0 ... 450.0 °C
K,T
–199.9 ... 750.0 °F
–199.9 ... 850.0 °F
–209.0 ... 850.0 °F
–200 ... 1370 °C
–250 ... 1420 °C
–250 ... 1420 °C
K
–320 ... 2500 °F
–370 ... 2550 °F
–370 ... 2550 °F
–200 ... 1000 °C
–250 ... 1050 °C
–250 ... 1050 °C
J
–320 ... 1800 °F
–370 ... 1850 °F
–370 ... 1850 °F
0 ... 1760 °C
–50 ... 1810 °C
–50 ... 1810 °C
R,S
0 ... 3200 °F
–50 ... 3250 °F
–50 ... 3250 °F
0 ... 1820 °C
–50 ... 1870 °C
–50 ... 1870 °C
B
0 ... 3300 °F
–50 ... 3350 °F
–50 ... 3350 °F
–200 ... 800 °C
–250 ... 850 °C
–250 ... 850 °C
E
–320 ... 1500 °F
–370 ... 1550 °F
–370 ... 1550 °F
–200 ... 1300 °C
–250 ... 1350 °C
–250 ... 1350 °C
N
–320 ... 2300 °F
–370 ... 2350 °F
–370 ... 2350 °F
0 ... 1390 °C
–50 ... 1440 °C
–50 ... 1440 °C
PL-
0 ... 2500 °F
–50 ... 2550 °F
–50 ... 2550 °F
0 ... 2315 °C
–50 ... 2365 °C
–50 ... 2365 °C
C(W/Re5-26)
0 ... 4200 °F
–50 ... 4250 °F
–50 ... 4250 °F
–199.9 ... 850.0 °C
–199.9 ... 900.0 °C
–210.0 ... 900.0 °C
–200 ... 850 °C
–210 ... 900 °C
–210 ... 900 °C
–199.9 ... 999.9 °F
–199.9 ... 999.9 °F
–211.0 ... 1099.9 °F
Pt100
–300 ... 1500 °F
–318 ... 1600 °F
–318 ... 1600 °F
–199.9 ... 500.0 °C
–199.9 ... 550.0 °C
–206.0 ... 550.0 °C
–200 ... 500 °C
–206 ... 550 °C
–206 ... 550 °C
–199.9 ... 900.0 °F
–199.9 ... 999.9 °F
–211.0 ... 999.9 °F
JPt100
–300 ... 900 °F
–312 ... 1000 °F
–312 ... 1000 °F
DC current and voltage inputs
(4 … 20 mA DC, 0 … 20 mA DC, 0 … 1 V DC, 0 … 5 V DC, 1 … 5 V DC, 0 … 10 V DC)
If input value exceeds Indication range high limit value, PV display blinks “
”, and if input value
exceeds the Indication low limit range, the PV display blinks “
”.
If input value exceeds the Control range, OUT1 and OUT2 are turned ON or OFF, depending on which
has been selected in the [Output status selection when input burnout] (for Control output analogue
current signal: OUT1 high or low limit value, OUT2 high or low limit value).
However, for manual control, it outputs the preset manipulated variable.
Indication range
: [Scaling low limit value – Scaling span x 1 %]
to [Scaling high limit value +Scaling span x 10 %]
(If the input value exceeds the range –1999 … 9999, the PV display blinks
“
” or “
”)
Control range
: [Scaling low limit value – Scaling span x 1 %]
to [Scaling high limit value +Scaling span x 10 %]
DC input burnout
: When DC input is burnt out, PV display blinks “
” for 4 … 20 mA DC
and 1 … 5 V DC inputs, and “
” for 0 … 1 V DC input.
For 0 … 20 mA DC, 0 … 5 V DC and 0 … 10 V DC inputs, the PV display
indicates the corresponding value with which 0 mA or 0 V is inputted.