WIKA CS4S User Manual

Page 18

background image

Operating Instructions Temperature Indicating Controller CS4S

V1.1

10/2006

- 18 -

OUT1 low limit setting
• Sets the low limit value of OUT1.

Not available when OUT1 is ON/OFF action.

• Setting range: –5 % to OUT1 high limit value

(Setting less than 0 % is only effective to Control output analogue

current signal)

0 %

OUT1 ON/OFF action hysteresis setting
• Sets ON/OFF action hysteresis for OUT1.
• Available only when OUT1 is ON/OFF action
• Setting range: 0.1 … 100.0 °C (°F) or 1 … 1000

1.0 °C

OUT2 action mode selection
• Selects OUT2 action from air, oil and water coolings.
• Not available when the option [DT2] is not added or when OUT2 is

ON/OFF action

• Air cooling:

, oil cooling:

, water cooling:

Air cooling

OUT2 high limit setting
• Sets the high limit value of OUT2.
• Not available when the option [DT2] is not added or when OUT2 is

ON/OFF action

• Setting range: OUT2 low limit value to 105 %

(Setting greater than 100 % is effective to DC current output type)

100 %

OUT2 low limit setting
• Sets the low limit value of OUT2.
• Not available when the option [DT2] is not added or when OUT2 is

ON/OFF action

• Setting range: –5 % to OUT2 high limit value

(Setting less than 0 % is effective to DC current output type)

0 %

Overlap band/Dead band setting
• Sets the overlap band or dead band for OUT1 and OUT2.

+ setting value: Dead band, – setting value: Overlap band

• Available only when the option [DT2] is added
• Setting range: –100.0 … 100.0 °C (°F) or 1 … 1000

0 °C

OUT2 ON/OFF action hysteresis setting
• Sets ON/OFF action hysteresis for OUT2.
• Available only when the option [DT2] is added
• Setting range: 0.1 … 100.0 °C (°F) or 1 … 1000

1.0 °C

A1 action selection
• Selects an action for A1.

No alarm action

:

Process high alarm

:

High limit alarm

:

Process low alarm

:

Low limit alarm

:

High limit alarm with standby :

H/L limits alarm

:

Low limit alarm with standby :

H/L limit range alarm :

H/L limits alarm with standby :

No alarm action

A2 action selection
• Selects an action for A2.
• Available only when option [2AS] or [2AL] is added
• Action selection and default value are the same as those of A1

action selection.

No alarm action

A1 action Energized/Deenergized selection
• Selects Energized/Deenergized for A1.
• Not available if No alarm action is selected in A1 action selection
• Energized:

Deenergized:

Energized

A2 action Energized/Deenergized selection
• Selects Energized/Deenergized for A2.
• Not available if option [2AS] or [2AL] is not added or if No alarm

action is selected in A2 action selection

• Action selection and default value are the same as those of A1

action Energized/Deenergized selection.

Energized