beautypg.com

DuraVent Type B Gas Vent User Manual

Page 7

background image

7

3. Ceiling Support. For a ceiling supported

system, install the Square Firestop/Support as

shown in Figures 6, 7, and 8. The Firestop

Support must be framed in and the dimensions

are shown in Table 1 and shown in Figure 4.

Firestop Supports are currently manufactured

for pipe sizes of 3” through 12” only. Larger

sizes may be locally fabricated from sheet

metal, provided that the mandatory 1-inch

clearance is maintained, the pipe is adequately

supported, and the installation is acceptable

to Local authorities. In multistory buildings,

a Firestop/Spacer must be provided at every

floor /ceiling level other than the first floor

which requires a support.

4. Wall Thimble. For a through-the-wall

system, install the Wall Thimble, as shown in

Figure 5. The Wall Thimble is designed to

accommodate walls up to 6 inches thick. If

you have thicker walls, a sleeve extension

should be fabricated and attached to the

existing sleeve . Do not fill the air space

between the B-vent pipe Section and the Wall

Thimble with insulation, although an RTV-type

sealant may be applied around the flange and

nail heads if desired.

5. Pipe Assembly. Sections of DuraVent

round pipe are joined together by lining up the

female end of the locking lug with the male

end slot, pushing them together, and turning

clockwise to twist lock. Refer to Figure 9.

Sheet metal screws are not needed for 3”

through 8” diameter pipe. However, if desired,

use 1/4-inch long sheet metal screws for 3”

through 8” diameter pipe. never penetrate

the inner liner with screws. For 10” through

16” diameter pipe, DuraVent recommends

using a minimum of (4) 3/8” sheet metal screws

per joint, and a minimum of (6) 3/8” sheet metal

screws are required per joint for 18” and larger

diameters. Each pipe Section is labelled, and

an arrow shows the direction of the exhaust flow.

Figure 7

HanGER

STRapS

Figure 8

cLaMp

pIpE cOLLaR

(OpTIOnaL)

B-VEnT pIpE

SEcTIOn

naILS

(4 REQ)

For ceiling supported installations, place a pipe

Section, or assembled pipe Sections, through

the hole in the Square Firestop Support, and

tighten the clamp. The clamp will rest inside the

ceiling Support, and prevent the pipe Sections

from dropping down. The pipe Section(s) should

protrude a minimum of one inch below the ceiling.