a gas vent support or firestop spacer must be

provided where the vent passes through the

ceiling. The ceiling opening is framed, using

the same sized lumber as the existing joists,

to fit around the raised edge of the gas vent

support, which is pushed up into the ceiling

from below. The hanger straps are nailed to

the framing using 1 1/2-inch box nails to hold

the gas vent support firmly, and the clamp is

then tightened around the vent pipe. Firestop

spacers must be utilized in multistory buildings

at each level where the vent passes through

a floor.

Sections of pipe are connected to each other

by pushing them firmly together and twisting.

Screws are not required. If screws are desired,

for 3- to 6-inch diameter pipe, use 1/4-inch

sheet metal screws. For larger diameters up

through 16 inches, use 3/8-inch sheet metal

screws. For 18-inch and greater diameters,

use 3/8-inch sheet metal screws. under no

circumstances, penetrate the inner liner with

screws.

any portions of the vent assembly that extend

through accessible or occupied spaces must

be enclosed with an enclosure that is at least

1-inch away from vent pipe.