DuraVent Type B Gas Vent User Manual

Page 22

background image

22

4-INCH OVAL GAS VENT FOR

INSTALLATION IN 2” x 4” STUD

WALLS

MH6375 CATEGORY I APPLIANCES ONLY

Gas vent shall extend at least 2 feet above the

highest point where it passes through the roof,

and at least 2 feet higher than any portion of

the building within 8 feet. Install oval flashing,

storm collar, and oval vent cap.

Where pipe passes through the roof, maintain

1-inch minimum clearance to all combustibles.

attach base plate to wall furnace. Firestop

spacers shall be installed as shown, on all

floors other than the first floor. use ceiling plate

spacers at this level.

1. Saw out portion of header between studs

and install one firestop spacer.

2. nail the second firestop spacer in position,

after oval pipe is in place.

3. all floors above to be installed in the same

manner.

4. Maximum BTu input:

Single story - 85,000 BTu

Multistory - 65,000 BTu

To assemble, align the two pieces, and

push them together until they click.

OVaL pIpE

FIRESTOp SpacER

Use only vents labeled “For Exterior Use

Only”, above roofline. (Canada Only)

OVaL pIpE

FIRESTOp

SpacER

cEILInG pLaTE

SpacER

BaSE pLaTE

WaLL

FuRnacE

1 IncH MInIMuM

cLEaRancE TO

cOMBuSTIBLES