6-INCH OVAL GAS VENT FOR

INSTALLATION IN 2” x 6” STUD

WALLS

MH6375 CATEGORY I APPLIANCES ONLY

Ensure at least 1 inch clearance to all

combustibles, including the area the pipe

passes through the roof.

Install oval flashing, storm collar, and oval vent

cap.

Gas vent shall extend at least 2 feet above the

roof, and at least 2 feet higher than any portion

of the building within 2 feet.

attach base plate to 2” x 6” support. Firestop

spacers shall be installed as shown on all

floors.

1. Saw out portion of header between studs

and install one firestop spacer.

2. nail the second firestop spacer in position,

after oval pipe is in place.

3. additional floors above are installed in the

same manner.

Use only vents labeled “For Exterior Use

Only”, above roofline. (Canada Only)

OVaL pIpE

FIRESTOp

SpacER

FIRESTOp

SpacER

BaSE pLaTE

anD TEE

SuppORT

1 IncH MInIMuM

cLEaRancE TO

cOMBuSTIBLES

cap

STORM cOLLaR

ROOF FLaSHInG

OVaL

TEE

OVaL

pIpE

2” X 6” SuppORT