Combination cap, Bucket support – DuraVent Type B Gas Vent User Manual

Page 10

background image

10

where the B-vent should be located, assemble

the Bucket Support and Brackets. nail the

assembly to the bottom side of the joist

material as shown in Figure 14. after the

Support Bucket is in place, scribe and cut out

a hole in the sheet rock 1/8” larger than the

diameter of the Bucket, and nail into place.

Run the pipe Sections through the hole in the

Bucket Support, connect the Duraconnect

or Duraconnect II connector, and attach the

clamp so that it rests inside the Bucket, and

will support the pipe. adjust the pipe to the

desired height and tighten the clamp. This

will provide a complete engineered support

system.

COMBINATION CAP

1. Description. The combination cap,

provides an easily installed, safe and efficient

B-Vent cap and Flashing, as one lightweight

unit. The two basic components and the

assembled unit are shown in Figure 15. The

combination cap is designed to accommodate

roof pitches from flat to 6/12, and is available

for 3” through 6” diameter B-Vent pipe.

2. Location. Locate the point in the underside

Figure 13

Figure 14

B-VEnT

BucKET

SuppORT

RaFTER 16 OR

24 IncHES O.c.

cEILInG

SInGLE-WaLL

cOnnEcTOR

(DuRa-cOnnEcT)

cOnTInuaTIOn

OF B-VEnT

naIL

HERE

TABLE 2

Gas vent systems using vent caps listed by underwriters laboratories may

terminate in accordance with this vent termination table

ROOF PITCH

MINIMUM HEIGHT

FEET

METERS

FLaT TO 7/12

1

0.3

OVER 7/12 TO 8/12

1.5

0.46

OVER 8/12 TO 9/12

2

0.61

OVER 9/12 TO 10/12

2.5

0.76

OVER 10/12 TO 11/12

3.25

0.99

OVER 11/12 TO 12/12

4

1.22

OVER 12/12 TO 14/12

5

1.52

OVER 14/12 TO 16/12

6

1.83

OVER 16/12 TO 18/12

7

2.13

OVER 18/12 TO 20/12

7.5

2.29

OVER 20/12 TO 21/12

8

2.44

BUCKET SUPPORT

1. Description. The Bucket Support (Figure

13) is for properly supporting the B-vent

between 16 or 24-inch O.c. joists or rafters,

or for providing a transition fitting between

Duraconnect or Duraconnect II and the B-vent

pipe Sections. a maximum of 20 feet of Type

B Gas Vent may be supported. note that the

Bucket Support must be installed prior to the

sheetrock.

2. Assembly. after you have determined

B-VEnT

MuST

EXTEnD a

MInIMuM

OF 1"

BELOW

THE

FInISHED

cEILInG