beautypg.com

Troubleshooting – DuraVent Type B Gas Vent User Manual

Page 17

background image

17

to obtain a specific location for the appliance.

Make a mark on the horizontal pipe Section

flush with the vertical face of the masonry, for

referencing the vertical position. Slip a pipe

collar over the horizontal pipe Section and

install the remaining fittings as shown in Figure

30. a minimum of 12 inches of connector rise

is required.

(i). Insulation. pull the pipe collar towards

the 90° Elbow. Fill in the gap between the

masonry and the horizontal pipe Section with

ceramic fiber insulation, as shown in Figure

31. The filling may be faced off with grout, if

desired. push the pipe collar back flush with

the masonry. Make any final adjustments

on the adjustable Length pipe (if used), and

tighten the clamping bolts.

TROUBLESHOOTING

1. Purpose. This section is intended as a

general maintenance and troubleshooting

guide, and as such, cannot encompass all

configurations or vent designs. For problems

encountered which are beyond the scope

of this sheet, contact your DuraVent Dealer,

Distributor, or DuraVent’s Engineering

Department. It is imperative that the one-

inch clearance (air space) defined in these

instructions be maintained. In most cases,

a one-inch minimum clearance must be

maintained to combustibles. The only

exceptions are 4-inch, 5-inch and 6-inch Oval

B-vent which are installed within stud walls.

Oval B-vent and BW Vent are the subject of

a separate section of these instructions For

Oval B-vent,, the clearances are established

by the listed Firestop Spacers described in the

instructions for Oval B-Vent.

2. Appliance. Read the appliance installation

instructions carefully, ensuring that the

prescribed clearances are met, and that it is a

category I appliance.

3. Spillage. Spillage from an appliance draft

hood may cause condensation on windows, or

odors that the occupant may notice. Spillage

may be caused by an incorrectly sized vent

system, blockage of the vent system, or a

downdraft in the vent. Other causes are:

excessive lateral runs, too many elbows,

improper pitch to lateral runs (a minimum of

1/4 inch per foot of run is correct), fans or

ventilation systems in the same general area

as the gas appliance, or wind conditions at the

vent cap.

4. Blockage. check the system for blockage

by removing the cap, and looking down into

the vent with a flashlight. check for bird nests,

debris, rodents, insects, or other obstructions.

If nothing is found, inspect the entire system

for physical damage.

5. Downdraft. Downdrafts are generally

caused by the system’s termination being too

close to an adjacent wall, parapet, or other

structure. If the cap is within eight feet of such

an obstruction, it must also be at least two feet

above it. also ensure that the top is at the

height prescribed for your roof pitch in Table

2. Inadequate combustion air is also a major

cause of downdraft problems. appliances like

clothes dryers or other exhausting appliances

in the same utility room can cause downdraft

problems.

6. Condensate/Corrosion. continuous

condensate can cause corrosion (rusting) of

vents, tops, appliance draft hoods, and other

components of the system, as well as the

inside of the appliance. This situation can be

extremely dangerous, and corrective action

must be taken immediately. common causes

of corrosion are listed below: If in doubt call a

professional to inspect the vent.

(a) If the vent system is located in an area

where spray cans or solvents are used

extensively, (laundry areas, or paint shops,