Installation, Preinstallation, Pump location guidelines – Goulds Pumps 3198 i-FRAME - IOM User Manual
Page 21
Installation
Preinstallation
Precautions
WARNING:
• When installing in a potentially explosive environment, make sure that the motor is properly certified.
• You must earth (ground) all electrical equipment. This applies to the pump equipment, the driver, and
any monitoring equipment. Test the earth (ground) lead to verify that it is connected correctly.
NOTICE: Supervision by an authorized ITT representative is recommended to ensure proper installation.
Failure to do so may result in equipment damage or decreased performance.
Pump location guidelines
WARNING:
Assembled units and their components are heavy. Failure to properly lift and support this equipment can
result in serious physical injury and/or equipment damage. Lift equipment only at the specifically identified
lifting points. Lifting devices such as eyebolts, slings, and spreaders must be rated, selected, and used for
the entire load being lifted.
Guideline
Explanation/comment
Keep the pump as close to the liquid source as
practically possible.
This minimizes the friction loss and keeps the
suction piping as short as possible.
Make sure that the space around the pump is
sufficient.
This facilitates ventilation, inspection, maintenance,
and service.
If you require lifting equipment such as a hoist or
tackle, make sure that there is enough space
above the pump.
This makes it easier to properly use the lifting
equipment and safely remove and relocate the
components to a safe location.
Protect the unit from weather and water damage
due to rain, flooding, and freezing temperatures.
This is applicable if nothing else is specified.
Do not install and operate the equipment in
closed systems unless the system is constructed
with properly-sized safety devices and control
devices.
Acceptable devices:
• Pressure relief valves
• Compression tanks
• Pressure controls
• Temperature controls
• Flow controls
If the system does not include these devices, consult
the engineer or architect in charge before you operate
the pump.
Take into consideration the occurrence of
unwanted noise and vibration.
The best pump location for noise and vibration
absorption is on a concrete floor with subsoil
underneath.
If the pump location is overhead, undertake
special precautions to reduce possible noise
transmission.
Consider a consultation with a noise specialist.
Installation
Model 3198 i-FRAME Installation, Operation, and Maintenance Manual
19