beautypg.com

Myron L 760-A Aquaswitch User Manual

Page 11

background image

3.3 OPERATIONAL CHECKOUT PROCEDURES
The following checkout procedures are used to verify that the

Aquaswitch or 760-A Aquaswitch is operating properly.
NOTE:

To complete the checkout procedure, it is assumed that the system

is fully installed and the Aquaswitch is connected to a reliable

resistivity Controller or a 760-A Aquaswitch is installed. It is also

assumed that two fresh Dl banks are on line with the system and

the Controller is indicating water quality in the desired range.
During this test procedure, it will be necessary to simulate GOOD

and POOR water quality. This is done by setting the Set Point

to BELOW or ABOVE the Controller’s actual water resistance

reading. When the Set Point is set BELOW (counterclockwise),

the monitor will simulate “GOOD” water quality. “POOR” water

quality is simulated by setting the Set Point ABOVE (clockwise)

the actual water quality.
3.3.1 760-A AQUASWITCH (ONLY)
STEP 1 Using the “SET POINT CHECK” switch, verify that the

meter indicates the desired Set Point.

NOTE:

If the meter does not indicate the correct Set Point setting, reference

Section 4.5.2 for the procedures to readjust the 760-A Aquaswitch’s

internal Set Point.
STEP 2 Observe resistance reading of water being monitored.
STEP 3 With front panel removed, depress “SET POINT CHECK”

switch and observe the reading on the analog meter. With

a small screwdriver, adjust the Set Point trimmer (R31)

(See Fig. 4-1) to above the reading observed in STEP 2.

Release the “SET POINT CHECK” switch and observe

that the red “POOR” light is ON.

STEP 4 Depress the “SET POINT CHECK” switch and adjust

screw adjustment (R31) until the Set Point is below the

reading observed in STEP 2. Release the “SET POINT

CHECK” switch and observe that the green “ABOVE”

light is ON. Also note the audible click of the relay as the

lights change.

STEP 5 Readjust the Set Point trimmer (R31) to the desired Set

Point setting and replace front panel. This completes the

760-A Aquaswitch Control board checkout.

3.3.2 AQUASWITCH / 760-A AQUASWITCH
NOTE:

For 760-A Aquaswitch users, the term “Controller” refers to the

760-A Control Board functions.
STEP 1 Turn the Purge Cycle trimmer adjustment screw (R2) fully

clockwise to obtain an approximate one minute cycle.

(See Fig. 4-1)

STEP 2 Adjust Controller “Set Point” to simulate “GOOD” water

quality (for the 760-A Aquaswitch, turn the Set Point

trimmer adjustment screw (R31) counterclockwise (see

Section 4.5.2)) and verify the following sequence of

operation.

STEP 3 Push “BANK SWITCH” several times to verify the following

Controller operations.

3.1 Verify that the “IN USE” indicator lights switch

ON and OFF between Banks A and B each time

“BANK SWITCH” is pressed.

3.2 Verify that both Banks A/B “GOOD” water quality

lights remain ON.

3.3 Verify that the “BLEED” light remains OFF.

3.4 Leave BANK A ON for next step. (If required,

push the “ALARM RESET” switch to reset

alarm.)

NOTE:

If the Logic Module Alarm Reset jumper has been installed to provide

the user with the optional Manual Bank Switch alarm condition, the

alarm will be activated each time the “BANK SWITCH” is pressed.

Otherwise, the alarm will be activated only when the Purge Cycle

time setting has expired. (Refer to Section 4.4)
STEP 4 Adjust Controller Set Point to simulate “POOR” water

quality. (For the 760-A Aquaswitch, turn Set Point trimmer

adjustment screw (R31) clockwise, and verify the following

sequence of operation.)
4.1 BANK A water quality indicates “POOR.”

4.2 Yellow “BLEED” light turns ON and water is

purged from system. (This should continue for

about 1 minute.)

4.3 After 1 minute, BANK A will turn OFF and BANK

B will turn ON and indicate “POOR” water

quality.

4.4 After approximately 1 minute, BANK B should

turn OFF, the “BLEED” light should turn OFF, the

Bleed valve should close and the alarm should

be activated. The system is now entirely shut

down.

NOTE:

If an external alarm is connected, it will be activated when the

Aquaswitch switches Banks. (Press the “ALARM RESET” switch

to turn OFF alarm.)
If an alarm is not connected, an alarm condition can be monitored

by connecting an ohm meter across Power Module Terminals TB3-

2 and TB3-3. The meter should indicate a CLOSED CIRCUIT in

the alarm condition.
STEP 5 Adjust the Controller Set Point to simulate “GOOD” water

quality. (For the 760-A Aquaswitch, turn Set Point trimmer

adjustment screw (R31) counterclockwise and verify the

following sequence of operation.)

STEP 6 Press the “BANK SWITCH.” The BANK A “IN USE” and

“GOOD” water quality indicator lights should turn ON.

Press the “BANK SWITCH” again and BANK B “IN USE”

and “GOOD” water quality indicator lights should turn

ON.

STEP 7 Complete the following steps to return the Aquaswitch to

its normal operating status.
7.1 Using the “BANK SWITCH,” select the desired

Bank “IN USE” status.

7.2 Adjust the Controller “Set Point” to the desired

minimum water quality. (Refer to Section

4.5.2)

7.3 Set Purge Cycle to the desired time delay. (Refer

to Section 4.3)

9

This manual is related to the following products: