Control terminal connections, Operation – Beijer Electronics Industrial Inverter E2 User Manual
Page 16

16
4.11.
Control Terminal Connections
Default Connections
Control
Terminal
Signal
Description
1
+24V User Output,
+24V, 100mA.
2
Digital Input 1
Positive logic
“Logic 1” input voltage range: 8V … 30V DC
“Logic 0” input voltage range: 0V … 4V DC
3
Digital Input 2
4
Digital Input 3 /
Analog Input 2
Digital: 8 to 30V
Analog: 0 to 10V, 0 to 20mA or 4 to 20mA
5
+10V User Output
+10V, 10mA, 1kΩ minimum
6
Analog Input 1 /
Digital Input 4
Analog: 0 to 10V, 0 to 20mA or 4 to 20mA
Digital: 8 to 30V
7
0V
User ground connected terminal 9
8
Analog Output /
Digital Output
Analog: 0 to 10V, 20mA maximum
Digital: 0 to 24V
9
0V
User ground connected terminal 7
10
Relay Common
11
Relay NO Contact
Contact 250Vac, 6A / 30Vdc, 5A