20"
16"
Lights
on Door
Supply
Mix
Recirculate
Exhaust (MRSE-D Only)
Start/Mode
Button
Stop
Button
Optional
Modulating Temperature Control
Ground
No Field
Connection
Neutral
120VAC
Red
White
Red
RTD (Optional)
24 VDC +
24 VDC Remote Cool Thermostat
24 VDC Remote "Supply On"
24 VDC Remote "Mix On"
24 VDC Remote "Recirculate On"
24 VDC Remote "Exhaust On"
24 VDC Remote "Stop"
C u s t o m e r S u p p l i e d C o n t r o l s Fo r E x t e r n a l I n p u t
Load
Fan Motor
Line
Fan Voltage
5VDC-10VDC POS
24VAC COM / 5VDC-10VDC
24VAC
3
Black
Red
4
5
NC
NC
Damper Actuator Connections
G N
N
L
L
R
RW 1 2345678910ABCTTT
Wiring Installation
All wiring should be in accordance with local ordinances
and the National Electrical Code, NFPA 70. Ensure the
power supply (voltage, frequency, and current carrying
capacity of wires) is in accordance with the motor name-
plate. Refer to the
Wiring Diagram
, below.
Fan accessories will determine the wiring installation
procedure you should follow. If your unit has a disconnect
switch, follow the wiring diagram provided on the discon-
nect switch and the wiring diagram on the motor. Correctly
label the circuit on the main power box and always identify
a closed switch to promote safety (i.e. red tape over a
closed switch).
Lock off all power sources before unit is wired to
power source. Restrain the wire as necessary to pre-
vent it from being pulled into any rotating parts.
Fan Wiring
Drill a wire access hole through the cabinet side below
one of the access doors. Attach the appropriate size wire
and conduit to the motor and run the wires to the control
panel. Attach wires (18 gauge minimum) to the damper
actuator (Red, Black, #3) and the temperature sensor (Red,
2-Black), if equipped, and run the wires to the control
panel. Attach the fan wires to the control panel terminals
according the diagram below.
A terminal (1) is available for use with remote stop con-
trols. Closing a relay between terminals 1 and 5 will do the
same function as pushing the stop button on the front of the
panel.
Wire the roof disconnect switch, if equipped, and the fan
motor. The fan should rotate clockwise, when looking up
from the bottom, in supply mode. The rotation may be
changed by switching two of the three motor leads. When
rotation is correct, reinstall the access panels.
Control Panel Wiring Diagram