Balboa Water Group BP 60Hz User Manual
Page 58
![background image](/manuals/458355/58/background.png)
58
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417, 834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. All material copyright of Balboa Water Group.
4/22/13
Settings
Back
Light Cycle
Invert Panel
Normal
Lock
Hold
Preferences
Information
Utilities
Back
Utilities
A/B Temps Off
Demo Mode
Off
Fault Log
GFCI Test
Back
Test
Reset
GFCI Status - Passed
THE GROUND FAULT CIRCUIT INTERRUPTER (GFCI)
The Ground Fault Circuit Interrupter (GFCI) or Residual Current
Detector (RCD) is an important safety device and is required
equipment on a hot tub installation. (The GFCI Test Feature is
not available on CE rated systems.)
USED FOR VERIFYING A PROPER INSTALLATION
Your spa may be equipped with a GFCI Protection feature. If your
spa has this feature enabled by the manufacturer, the GFCI Trip
Test must occur to allow proper spa function.
Within 1 to 7 days after startup, the spa will trip the GFCI to test
it. (The number of days is factory programmed.) The GFCI must
be reset once it has tripped. After passing the GFCI Trip Test,
any subsequent GFCI trips will indicate a ground fault or other
unsafe condition and the power to the spa must be shut off until
a service person can correct the problem.
FORCING THE GFCI TRIP TEST
The installer can cause the GFCI Trip Test to occur sooner by
initiating it using the above menu.
The GFCI should trip within several seconds and the spa should
shut down. If it does not, shut down the power and have a quali-
fied person verify that the GFCI breaker is installed and that the
circuit and spa are wired correctly. Verify the function of the GFCI
with its own test button. Restore power to the spa and repeat
the GFCI Trip Test.
Once the GFCI is tripped by the test, reset the GFCI and the spa
will operate normally from that point. You can verify a successful
test by navigating to the above menu. PASS should appear after
a temp button is pressed from the GFCI Screen.
WARNING:
The end-user must be told to expect this one-time test to
UÊ
occur and how to properly reset the GFCI.
If
UÊ
freezing conditions exist, the GFCI should be reset imme-
diately or spa damage could result.
CE PRODUCT:
CE registered systems do not have an RCD Test Feature due
UÊ
to the nature of the electrical service.
Some UL registered systems do not have the GFCI Test
UÊ
Feature activated.
The end-user must be trained how to properly test and reset
UÊ
the RCD.
TP800, TP900 Sensor and System Related Messages (cont.)