3.0 OPERATION INSTRUCTIONS
WARNING: Do not force the gas control knob. Use only your hand to turn the gas
control knob. Never use any tool. If the gas control knob will not operate by hand
the gas control should be replaced by a qualified service technician.
WARNING: Do not disassemble the gas control; it contains no replaceable
components. Attempted disassembly or repair may damage the gas control.
WARNING: In the event of main burner ignition failure, a 5 minute purge period
must be observed prior to re-establishing ignition source.
For CSD-1 equipped boilers, see section 4.0 for Operation Instructions for CSD-1
Equipped Boiler.
BOILER CONTROLS (Inside Cabinet)
Main Power Switch
-
ON fills the boiler tank and turns the boiler controls on.
You should allow 20 minutes to fill the tank and generate
steam.
-
OFF shuts off the boiler controls and opens the automatic
blowdown valve, emptying the boiler tank and releasing
water and steam to the drain. This should be done at least
once daily to remove sediment, lime, or scale.
Pilot Light
-
Indicates main power is ON.
Boiler Pressure Gauge -
Should read 9 -11 psi during operation; 0 psi during
shutdown.
Water Level Sight Glass -
Observe level of water in the boiler and water quality.
Murkiness in the water indicates inadequate water quality;
the owner must supply proper water to the boiler (see page
4, Water Quality Statement).
Water Level Control
-
While ON, briefly open the water level control daily to
remove any sediment that might accumulate.
Safety
-
This valve will release (pop off) if the boiler has too much
pressure. Once a week, this valve should be tripped
during operation to make sure it functions properly.
CAUTION: If you smell gas during the lighting procedure, immediately shut off the
gas supply until the leak has been corrected.