beautypg.com

Troubleshooting – Blodgett SB-E Series User Manual

Page 21

background image

OM-E-SB 19

Troubleshooting

SYMPTOM

WHO

WHAT TO CHECK

Boiler builds pressure but

shuts down. RESET light

comes on.

User

a. Is the water level below the “mid” water level probe? Verify that

the water supply is sufficient to maintain the water level at or above

the “mid” water level probe.

Authorized

Service Rep Only

b. Is the operating pressure switch defective? No adjustment is

allowed. Replace the switch if defective. NOTE: If the high-limit

pressure switch has shut down the unit, it should not be restarted

until the problem which caused the shut-down has been corrected.

(X)

c. Is the “mid” water level probe unable to detect water? Clean the

water level probe and probe well (located in the boiler). (X)

Safety relief valve opens.

Authorized

Service Rep Only

a. Are the operating pressure switch and/or high-limit pressure

switch defective? No adjustment is allowed. Replace defective

switches. (X)

b. Is the safety relief valve defective? Replace with ASME approved

15 PSI valve with “HV” marking. (X)

Boiler blows down

immediately when turned off.

Authorized

Service Rep Only

a. Is the thermostatic switch defective? Check for loose electrical

connections on switch. (X)

Boiler does not drain.

Authorized

Service Rep Only

a. Is the thermostatic switch defective? (X)

b. Is the solenoid drain valve defective? (X)

c. Are the solenoid drain valve or hoses blocked? (X)

Boiler does not build pressure

with heaters on.

User

a. Is the steam power take-off valve open or leaking?

b. Is the pressure gauge defective?

Authorized

Service Rep Only

c. Is the air vent leaking steam? (X)

d. Is the solenoid or manual drain valve open or leaking?

NOTE: Excessive make-up water added to the boiler reduces

steam production. (X)

Timer control will not operate.

User

a. Is the electrical supply turned on?

b. Is the ON/OFF switch in the base cabinet turned on?

c. Is boiler started? Is the green light in the ON/OFF switch lit?

d. Are any fuses blown?

No steam to cavities.

User

a. Has steam pressure developed?

b. Is steam supply turned on?

c. Is the door closed? (Doors must be closed before steam will

enter the cavity).

Door leaking steam or water.

User

a. Are the drain holes at the rear of the cavity blocked?

b. Does the door gasket need replacement?

c. Is the door latch in need of adjustment?

(See the Maintenance section).

d. Is the unit level?

Excessive steam coming from

the vent pipe.

User

a. Is the water supply turned on?

b. Is the condenser hose kinked or obstructed?

c. Is the condenser spray solenoid working?