Installation

Ventilation

Blodgett gas deck ovens are direct fired. Heat and flue

products from the burners are introduced directly into the

baking compartment. As a result, improper venting can

have a detrimental effect on the baking characteristics

of the oven. A properly designed ventilation system will

allow the oven to function properly, while removing un-

wanted vapors and products of combustion from the op-

erating area.
This oven may be vented using either:
• A mechanically driven, canopy type, exhaust hood,

or

• A direct flue arrangement.
U.S. and Canadian installations
Refer to your local ventilation codes. In the absence of

local codes, refer to the National ventilation code titled,

“Standard for the Installation of Equipment for the Remov-

al of Smoke and Grease Laden Vapors from Commercial

Cooking Equipment”, NFPA-96-Latest Edition.
General export installations
Installation must conform with Local and National instal-

lation standards. Local installation codes and/or require-

ments may vary. If you have any questions regarding the

proper installation and/or operation of your Blodgett oven,

please contact your local distributor. If you do not have a

local distributor, please call the Blodgett Oven Company

at 0011-802-658-6600.
The Blodgett Oven Company cannot assume responsi-

bility for loss or damage suffered as a result of improper

installation..

WARNING:

Failure to properly vent the oven can be haz-

ardous to the health of the operator and may

result in operational problems, unsatisfactory

baking and possible damage to the equip-

ment.
Damage sustained as a direct result of im-

proper ventilation will not be covered by the

Manufacturer’s warranty.

CANOPY TYPE EXHAUST HOOD
A mechanically driven, canopy type exhaust hood is the

preferred method of ventilation.
The hood should be sized to completely cover the equip-

ment plus an overhang of at least 6” (15 cm) on all sides

not adjacent to a wall. The distance from the floor to the

lower edge of the hood should not exceed 7’ (2.1m).
The capacity of the hood should be sized appropriately

with provisions for an adequate supply of make up air.

Capacity is generally expressed in ft3/min (CFM). 1 CFM

of natural gas burned with just enough air for complete

combustion produces 11 CFM of combustion products.

In virtually all appliances some excess air is used. This

volume of excess air is added to the flue products flowing

from the appliance.
NOTE: Consult your local exhaust hood contractor for

your specific installation.

Installing the canopy hood draft diverter
Ovens ordered for hood venting are supplied with a draft

diverter. Install the draft diverter as follows:
1. Place the diverter over the flue connector with the

open area facing the front of the oven.

2. Secure both ends with the sheet metal screws pro-

vided.

Draft Diverter

Front of Oven

Figure 6