Instruction manual BFC

76

F03 (lock out error)

The pressure switch

fails to work correctly

Damaged wiring/Open

circuit

1. Check the wiring between the pressure switch and the

controller

2. If necessary, replace the wiring

If the error cannot be resolved or is persistent, contact your

installation engineer
To replace the necessary parts, you must contact your installation

engineer

Pressure switch not

closing

1. Check the running speed of the fan

(12.5 "Display the selected

appliance")

2. Check that the hoses on the pressure switch and the air supply

hose between fan and burner are correctly fitted. Refit them if
necessary

3. Check for cracks in the hoses on the pressure switch and in the

air supply hose between fan and burner. If necessary, replace
the hoses.

4. Check that the flue gas outlet is compliant

(3.9 "Air supply and

flue")

.

5. Check for blockage in the flue gas discharge. Remove any

blockage that may be present

6. Check for blockage in the condensation water discharge.

Remove any blockage that may be present.

7. Measure the pressure differential across the pressure switch.

See the table in Preparation for
maintenance

(15.2 "Preparation for maintenance")

. If there is

insufficient pressure differential, clean the heat exchanger. If the
pressure differential is acceptable, check that the pressure
switch is closing, using a multimeter.

Code + Description

Cause

Solution

Remark