is

Instruction manual BFC

73

S12 (blocking error)

Short circuit in sensor 1

of temperature sensor

T

1

at the top of the

tank

(1)

Short circuit in sensor

circuit

Replace sensor T

1

To replace the necessary parts, you must contact your installation

engineer

S13 (blocking error)

Short circuit in sensor 2

of temperature sensor

T1 at the top of the

tank

(1)

Short circuit in sensor

circuit

Replace sensor T

1

To replace the necessary parts, you must contact your installation

engineer

S14 (blocking error)

Short circuit from

dummy 1

Short circuit in sensor

circuit

Replace the dummy sensor

(2)

To replace the necessary parts, you must contact your installation

engineer

S15 (blocking error)

Short circuit from

dummy 2

Short circuit in sensor

circuit

Replace the dummy sensor

(2)

To replace the necessary parts, you must contact your installation

engineer

F01 (blocking error)

Defect in power supply

circuit

Live and neutral

connected wrong way

round

Connect live and neutral correctly

(3.10 "Electrical connection")

;

the appliance is phase-sensitive

See the BFC electrical diagram

(17 "Appendices")

Condensation on the

flame probe

1. Disconnect the lead at the flame probe
2. Ignite the appliance three times, with an interrupted ionisation

circuit

3. Reconnect the ionisation lead to the flame probe
4. Ignite the appliance again
5. The repeated ignition attempts will have caused the

condensation to evaporate

If errors persist, contact your installation engineer

Floating neutral

Install an isolating transformer

(3.10.4 "Isolating transformer")

Contact your installation engineer to have an isolating transformer

installed

Code + Description

Cause

Solution

Remark