Instruction manual BFC

74

F02 (lock out error)

Fan fails to run at

correct speed.

Defective motor and/or

rotor.

1. Check the motor and rotor
2. Replace the fan if the motor or rotor is defective.
3. Reset appliance controller

See the BFC electrical diagram

(17 "Appendices")

To have the wiring replaced and a new fan fitted, you must contact

your installation engineer

Damaged wiring

1. Check the wiring between the fan and the controller.
2. If any wires are damaged, the wiring harness must be replaced.
3. Reset appliance controller

Dirty or blocked fan

1. Check if the fan is dirty
2. Check that the rotor can rotate freely
3. Reset appliance controller

Because of a drop in

the supply voltage, the

fan is not running at the

correct speed.

1. Check the supply voltage, this must be 230 VAC (-15%, +10%).
2. Reset appliance controller

The F02 entries below are applicable solely to appliances that have a 3-phase fan with frequency controller.
Fun supplying

insufficient pressure

The live (phase) wires,

between freq. controller

and fan are connected

wrong way around

1. Check the wiring between the fan and the frequency controller
2. Rectify the assembly if it is incorrect
3. Reset appliance controller

See the BFC electrical diagram

(17 "Appendices")

To replace the necessary parts, you must contact your installation

engineer

Fan speed too low

1. Check the fan speed
2. If the fan speed is too low, check the settings
3. If the settings are correct, then replace the fan.
4. Modify the settings if incorrect
5. Reset appliance controller

Code + Description

Cause

Solution

Remark