A.O. Smith 120 through 250 Series User Manual
Page 71

is
Instruction manual BFC
71
Water leakage
Leakage from a water
connection (threaded)
Tighten the threaded connection
If the leak persists, consult your installation engineer
Condensate leakage
Check that the condensation water discharge is working properly.
Rectify if necessary
Leakage from another
nearby water appliance
or pipe segment
Trace the leak
Leakage from the
appliance's tank
Consult the supplier and/or manufacturer
Explosive ignition
Incorrect supply
pressure and/or burner
pressure
Set the correct supply pressure and/or burner
pressure.
(3.11 "Checking the supply pressure and burner
If ignition is not improved, consult your installation engineer.
Contaminated burner
Clean the burner(s)
(15.4.2 "Clean the burner(s)")
Contaminated orifice
Clean the orifice(s)
(15.4.3 "Clean the orifice(s)")
Hot water supply
insufficient or absent
Appliance is turned off
Start the appliance up
No supply voltage
present
1. Check if the isolator is ON.
2. Check that there is power to the isolator.
3. Check whether the ON/OFF switch of the electronic controller is
ON (position I).
4. Check whether there is power to the electrical connector block.
5. The measured voltage must be 230 VAC (-15%, +10%).
See the BFC electrical diagram
If the error persists, consult your installation engineer.
Hot water supply is
used up
Reduce hot water consumption and give the appliance time to heat
up.
If there continues to be insufficient hot water, or none at all, consult
your installation engineer.
The controller is in OFF
mode.
Switch the controller to the ON mode
Temperature (T
set
) is
set too low.
(11.4 "Setting the water temperature")
temperature (T
set
) to
a higher value.
Symptom
Cause
Solution
Remark