Instruction manual BFC

75

Air pressure switch fails

to close during pre-

purge.

Air pressure switch

leads

1. Check the wiring between the air pressure switch and the

controller. Rectify any defect:
-

if any wires are damaged, replace the wiring harness

-

properly connect loose or detached hoses

2. Reset appliance controller

Loose air pressure

switch hoses

1. Check hoses between air pressure switch and burner/fan.

Rectify any defect:
-

if any wires are damaged, replace the wiring harness

-

properly connect loose or detached hoses

2. Reset appliance controller

Heat exchanger and/or

chimney flue is blocked

3. Measure the pressure differential across the air pressure switch
4. Check the values

(2.4.5 "Pressure switch")

5. Check heat exchanger, condensation drainage and/or chimney

flue for blockages

6. Clear any blockage that may be present.
7. Reset appliance controller

Defective controller

1. Check that the controller is receiving power
2. Check that the controller is correctly connected
3. If there is no electrical power, check the power supply to the

terminal block, or replace the controller.

4. Rectify any incorrect connections.
5. Reset appliance controller

Code + Description

Cause

Solution

Remark