beautypg.com

Air requirements, Combustion air “supply” ducts, Louvers and grills – American Water Heater DCG User Manual

Page 7: General

background image

7

Air Requirements

For buildings that are not well sealed (do not have tight

fitting doors and windows) natural air infiltration may

provide sufficient air required for combustion and venti-

lation. For buildings using tight construction (newer and

renovated structures), the air supply shall be introduced

from the outdoors, regardless of whether the space is

confined or unconfined.

Combustion Air “Supply” Ducts

Air supply ducts shall be of galvanized steel or equiva-

lent corrosion resistant material. A single air duct may

not be substituted when required for upper and lower

air openings. Horizontal upper combustion air ducts

shall not slope downward toward the air inlet.

Louvers and Grills

Openings for air supply ducts must provide free unob-

structed air movement. Louver and grill openings must

be sized to ensure that the FREE OPEN AREA is never

less than the area of the air duct.

LOCATION:

The location for top and bottom openings are as fol-

lows;
For U.S. installations:The top opening shall com-

mence within 12” (300 m) of the top of space and the

bottom opening shall commence within 12” (300mm) of

the bottom of the enclosure.
For Canadian installations:The top opening shall be

located as close to the ceiling as practical but never

lower than the relief opening of the lowest draft control

device. The bottom opening shall be located neither

more than 18 inches (450 mm), nor less than 6 inches

(150 mm), above floor level.

General

Where an exhaust fan or any other air consuming

appliance (Eg. Clothes dryer, furnace, etc.) is installed

in the same space as the water heater, sufficient air

openings must be available to provide fresh air when all

appliances are operating simultaneously.

The area in which the heater is located is classified as

either “an unconfined space” or “a confined space.”

An unconfined space is defined as a space having a

volume not less than 50 cubic feet per 1000 BTU/hour

(4.8 cubic meters per kilowatt) of combined input rating

of all appliances using the space. Adjacent open rooms

may be included as part of the unconfined space.

There shall be no closeable doors between these

rooms. An example of this is an open basement.

A confined space is one smaller than described above.

Air shall be supplied through permanent openings as

described in Figure 2. At no time shall an air opening

have a dimension of less than 3” (75 mm) and at no

time shall any top opening be lower than the top of the

water heater.

An adequate air supply shall be provided

for combustion and ventilation of this

water heater.

An insufficient supply can result in poor

combustion and possible sooting of the

burner, combustion chamber or flue

passageway. This may present a potential

fire hazard or could create a serious

health hazard by producing carbon

monoxide.

Index

This manual is related to the following products: