Temperature and Pressure

Relief Valve

For protection against excessive pressures and

temperatures, a temperature and pressure relief valve

must be installed in the opening marked “T & P RELIEF

VALVE” (See Figure 9). This valve must be design

certified by a nationally recognized testing laboratory

that maintains periodic inspection of the production of

listed equipment or materials as meeting the

requirements for Relief Valves and Automatic Shut-off

Devices for Hot Water Supply Systems, ANSI Z21.22.

(CSA4.4, Temperature, Pressure, Temperature and

Pressure Relief Valves and Vacuum Relief Valves in

Canada). The function of the temperature and pressure

relief valve is to discharge water in large quantities in

the event of excessive temperature or pressure devel-

oping in the water heater. The valve's relief pressure

must not exceed the working pressure of the water

heater as stated on the data plate.

Important: Only a new temperature and pressure relief

valve should be used with this water heater. Do not use

an old or existing valve as it may be damaged or not

adequate for the working pressure of the new water

heater. Do not place any valve or piping between the

relief valve and the tank.

The Temperature & Pressure Relief Valve:

Must not be in contact with any electrical part.

Must be connected to an adequate discharge

line.

Must not be rated higher than the working

pressure shown on the data plate of the water

heater.

The BTUH rating of the T & P valve must be

greater than, or equal to, the input rating of the

water heater.

The Discharge Line:

Must not be smaller than the pipe size of the

relief valve or have any reducing coupling

installed in the discharge line.

Must not be capped, blocked, plugged or

contain any valve between the relief valve and

the end of the discharge line.

• Must terminate a maximum of 6 inches (152mm)

above a floor drain or external to the building.

Must be capable of withstanding 250°F (121°C)

without distortion.

Must be installed to allow complete drainage of

both the valve and discharge line.

Figure 9: T&P Relief Valve

Explosion Hazard

If the temperature and pressure relief

valve is dripping or leaking, have a

qualified service technician replace it.

• Do not plug valve.

• Do not remove valve.

Failure to follow these instructions can

result in death or explosion.