WATER SYSTEM PIPING

Tempering Valve Installation

A Tempering Valve should be installed per the manufac-

turer’s instructions in the hot water line. See Figure 5

(below) for sample tempering valve installation.

Piping Installation

Piping, fittings, and valves should be installed according to

the installation drawing (Figure 4). If the indoor installation

area is subject to freezing temperatures, the water piping

must be protected by insulation.

Water supply pressure should not exceed 80% of the work-

ing pressure of the water heater. The working pressure is

stated on the water heater’s data plate. If this occurs, a

pressure reducing valve with a bypass should be installed

in the cold water inlet line to the entire system. This should

be placed on the supply to the entire structure in order to

maintain equal hot and cold water pressures.

Note: Water supplied to the unit that exceeds 12 grains

(205 mg/l) total hardness may reduce the life and perform-

ance of the water heater. Depending on the degree of hard-

ness, it is recommended that either a water pre-treatment

system or a water softener be installed and properly main-

tained.

Important: Heat cannot be applied to the water fittings on

the water heater as they may contain nonmetallic parts. If

solder connections are used, solder the pipe to the adapter

before attaching the adapter to the hot and cold water fit-

tings.

1. The water heater may have three water piping connec-

tion points. The top and front are 1 1/2” NPT and the

connections on the back of some heaters are 2” NPT.

When using front or back connections a nipple inlet

tube combination is required. For availability contact

1-800-456-9805.

Note: Inlet and outlet piping connections cannot

be mixed. For example, a top inlet connection must

use a top outlet connection.

2. The installation of unions in both the hot and

cold water supply lines is recommended for

ease of removing the water heater for service or

replacement.

3. Since most commercial installations utilize higher

temperatures, the use of a tempering valve is

strongly recommended in all domestic hot water

lines (i.e. public restroom sinks, etc).

4. If installing the water heater in a closed water

system, install an expansion tank in the cold water

line as specified under “Closed System/Thermal

Expansion” (Page 12).

5. Install a shut-off valve in the cold water inlet line.

It should be located close to the water heater and

be easily accessible. Know the location of this

valve and how to shut off the water to the heater.

6. The water heater is shipped with a factory-installed

Temperature and Pressure Relief Valve. Install a

discharge line in the opening in the T & P valve

(see instructions on Page 13).

7. After piping has been properly connected to the

water heater, remove the aerator at the nearest hot

water faucet. Open the hot water faucet and allow

the tank to completely fill with water. To purge

the lines of any excess air, keep the hot water

faucet open for 3 minutes after a constant flow of

water is obtained. Close the faucet and check all

connections for leaks.

Figure: 4 Water Piping Installation

Hot Water

Outlet

Unions

Cold Water

Inlet Valve

Discharge line

6” max. above

drain

Cold Water

Supply to Fixtures

In a closed system use a

Thermal Expansion Tank

Temperature and

Pressure Relief Valve

Drain line

3/4” ID min.

Drain

Metal drain

pan 1 3/4”

depth max.

Pressure Reducing

Valve with Bypass

Main Water

Supply

Massachusetts:

Install a vacuum relief

in cold water line per

section 19MGL 142

Space Heating

If this unit is to be used to supply both space heating and

domestic potable (drinking) water then the following

instructions must be followed:

1. All piping and components used must be suitable

for use with domestic (potable) drinking water.

2. Do not use piping or components that have been

connected to a nonpotable system or treated with

chromates or other toxic chemicals. Do not add any

chemicals to the water heater piping.

3. If system requires temperatures in excess of 120°F

(49°C) install a tempering valve, per the manufacturers

instructions, in the domestic (potable) hot water line

to limit the risk of scalding (See Figure 5).

4. Be sure to follow the manual(s) shipped with the

heating system. Also follow any state or local codes.

Figure 5: Tempering Valve

Follow the tempering

valve manufacturer’s

instructions.

Cold

Water

Inlet

Hot

Water

Outlet

Tempered water

to fixtures

Tempering valve

(Set to 120°F)