Ⅵ Square Root

The momentary flow rate Dx at a generated differential pressure of 16

I

W

(40%F.S.) is calculated by the following formula:
The coefficient k is determined by substituting the maximum momentary flow
rate Dm=120 and the then differential pressure Pm=80%F.S.(32

I

W) into the

formula (b) of the preceding paragraph 11.4 (1).

120

(Dx)

(Max.)

84.9

0

20

40

60

80

100

Differential Pressure

(%F.S.)

Momentary Flow Rate

(16

IW)

(32

IW)

k =

D

m

00

P

m

100

D

x

= kx

P

x

100

40
100

͌

͌

͌

120

80

100

͌

Therefore, the momentary flow rate Dx is determined by the formula (a) of
the preceding paragraph 11.4(1).

=

= 134.2

= 84.9

= 134.2

Ⅵ Setting example 4: Arbitrary unit of square root display mode

Setting of momentary flow rate

In order to set a momentary flow rate to an “arbitrary unit,” the
momentary flow rate unit must be set as the arbitrary unit, and the
maximum momentary flow rate of the arbitrary unit and the then
generated differential pressure must be set.