Aalborg Vortex Insertion User Manual
Page 89
![background image](/manuals/414129/89/background.png)
84
COMMAND
NAME
DESCRIPTION
NO.
COMMAND SYNT
A
X
COMMAND
ARGUMENT 1
ARGUMENT 2
ARGUMENT 3
ARGUMENT 4
RESPONSE
Pressure
Alarms**
Sets / reads the status of the
pressure alarms.
Note: High and Low limits have
to be entered in the Pa units.
High alarm value has to be
more than Low alarm value.
Alarm conditions:
Pressure > High Limit = H
Pressure. < Low Limit = L
Low < Press. < High = N
10
PA
H
(high press. limit)
alue> (0–Max.Press.) P A H: alue [P A]> L (low press. limit) alue> (0-Max.Press.) P A L: alue [Pa]> A (action delay in seconds) alue> (0-3600 sec.) P AA: alue [sec]> E (enable alarm) PA :E D (disable alarm)* PA :D R (read current status) P A R:N (no alarm) P A R:H (high alarm) P A R: L (low alarm) S (Read current settings) P AS:M,L,H,D,B where: M – mode (E/D) L – Low settings (Pa) H – High settings (Pa) D – Action Delay (sec) B – Latch mode (0-1) B Block (Latch) mode alue> (0-disabled*) (1-enabl’d ) P A B :< V al u e> w h er e: V alue = 0 – 1