You can display different bar graphs by selecting different variables from the
drop down menus at the top of each of the three bar graphs.

As with multimon, if you have your local host configured in the
/etc/apcupsd/hosts.conf file, you can execute it from a Unix shell from the
source cgi directory as follows:

./upsstats.cgi:

As with multimon, quite a few lines of html should then be displayed.

upsfstatus.cgi:

If you would like to see all of the STATUS variables available over the
network, click on the Data field of the desired system, and your browser
will display something like the following:

APC

: 001,048,1109

DATE

: Thu Dec 02 17:27:21 CET 1999

HOSTNAME : matou.sibbald.com
RELEASE

: 3.7.0-beta-1

CABLE

: Custom Cable Smart

MODEL

: SMART-UPS 1000

UPSMODE

: Stand Alone

UPSNAME

: UPS_IDEN

LINEV

: 223.6 Volts

MAXLINEV : 224.9 Volts
MINLINEV : 222.3 Volts
LINEFREQ : 50.0 Hz
OUTPUTV

: 223.6 Volts

LOADPCT

:

6.2 Percent Load Capacity

BATTV

: 27.9 Volts

BCHARGE

: 100.0 Percent

MBATTCHG : 5 Percent
TIMELEFT : 167.0 Minutes
MINTIMEL : 3 Minutes
SENSE

: High

DWAKE

: 060 Seconds

DSHUTD

: 020 Seconds

LOTRANS

: 196.0 Volts

HITRANS

: 253.0 Volts

RETPCT

: 050.0 Percent

STATFLAG : 0x08 Status Flag
STATUS

: ONLINE

ITEMP

: 35.1 C Internal

ALARMDEL : Low Battery