Interpretation of the old firmware revision – APC UPS control system User Manual
Page 197

= messages.
Bit
Meaning
0
Output unpowered due to shutdown by low battery
1
Unable to transfer to battery due to overload
2
Main relay malfunction - UPS turned off
3
In sleep mode from @ (maybe others)
4
In shutdown mode from S
5
Battery charger failure
6
Bypass relay malfunction
7
Normal operating temperature exceeded
Interpretation of the Old Firmware Revision
The Old Firmware Revision is obtained with the “V” command, which gives
a typical response such as “GWD” or “IWI”, and can be interpreted as
follows:
Old Firmware revision and model ID String for SmartUPS \& MatrixUPS
This is a three character string XYZ
where X == Smart-UPS or Matrix-UPS ID Code.
range 0-9 and A-P
1 == unknown
0 == Matrix 3000
5 == Matrix 5000
the rest are Smart-UPS and Smart-UPS-XL
2 == 250
3 == 400
4 == 400
6 == 600
7 == 900
8 == 1250
9 == 2000
A == 1400
B == 1000
C == 650
D == 420
E == 280
F == 450
G == 700
H == 700XL
I == 1000
J == 1000XL
K == 1400
L == 1400XL
M == 2200
N == 2200XL
O == 3000
P == 5000
where Y == Possible Level of Smart Features, unknown???
G == Stand Alone
T == Stand Alone
V == ???
W == Rack Mount
where Z == National Model Use Only Codes
D == Domestic
115 Volts
196