APC UPS control system User Manual

Page 190

background image

E

Automatic self test intervals

Default = 336 (336 hours = 14

days) (336=14 days, 168=7 days,
ON=power on, OFF=never)

F

Line frequency, Hz

60.00 (50.0 in Europe)

G

Cause of transfer

R = unacceptable utility voltage
rate of change, H = high utility
voltage, L = low utility voltage, T
= line voltage notch or spike, O
= no transfers yet (since turnon),
S = transfer due to serial port
U command or activation of UPS
test from front panel, NA = trans-
fer reason still not available (read
again).

K—K

Shutdown with grace period (set
with ’p’) - need > 1.5s between
first and second K

Matrix/3rd gen SmartUPS/Black
Back-UPS Pros: “OK”, all others:
“*”

L

Input line voltage

Ranges

-

typical

“118.3”

or

“228.8” in Europe

M

Maximum line voltage received
since last M query

Ranges

-

typical

“118.9”

or

“230.1” in Europe

N

Minimum line voltage received
since last N query

Ranges

-

typical

“118.9”

or

“226.2” in Europe

O

Output voltage

Ranges

-

typical

“118.3”

or

“228.8” in Europe

P

Power load %

Ranges - typical “011.4” depends
on what you have plugged in.

Q

Status flags

Bitmapped, see below

R

Turn dumb Only on 3rd gen Smar-
tUPS, SmartUPS v/s, BackUPS
Pro

“BYE”

S

Soft shutdown after ’p’ delay, re-
turn online when power returns
Only works when UPS is on bat-
tery

OK

U

Simulate power failure

!! when switching to battery, then
$ when back on line

V

Old firmware revision

“GWD” or “IWI” The last charac-
ter indicates the locale (Domestic,
International).

W

Self test (battery), results stored
in “X”

“OK”

189