APC UPS control system User Manual
Page 190

E
Automatic self test intervals
Default = 336 (336 hours = 14
days) (336=14 days, 168=7 days,
ON=power on, OFF=never)
F
Line frequency, Hz
60.00 (50.0 in Europe)
G
Cause of transfer
R = unacceptable utility voltage
rate of change, H = high utility
voltage, L = low utility voltage, T
= line voltage notch or spike, O
= no transfers yet (since turnon),
S = transfer due to serial port
U command or activation of UPS
test from front panel, NA = trans-
fer reason still not available (read
again).
K—K
Shutdown with grace period (set
with ’p’) - need > 1.5s between
first and second K
Matrix/3rd gen SmartUPS/Black
Back-UPS Pros: “OK”, all others:
“*”
L
Input line voltage
Ranges
-
typical
“118.3”
or
“228.8” in Europe
M
Maximum line voltage received
since last M query
Ranges
-
typical
“118.9”
or
“230.1” in Europe
N
Minimum line voltage received
since last N query
Ranges
-
typical
“118.9”
or
“226.2” in Europe
O
Output voltage
Ranges
-
typical
“118.3”
or
“228.8” in Europe
P
Power load %
Ranges - typical “011.4” depends
on what you have plugged in.
Q
Status flags
Bitmapped, see below
R
Turn dumb Only on 3rd gen Smar-
tUPS, SmartUPS v/s, BackUPS
Pro
“BYE”
S
Soft shutdown after ’p’ delay, re-
turn online when power returns
Only works when UPS is on bat-
tery
OK
U
Simulate power failure
!! when switching to battery, then
$ when back on line
V
Old firmware revision
“GWD” or “IWI” The last charac-
ter indicates the locale (Domestic,
International).
W
Self test (battery), results stored
in “X”
“OK”
189