Voltage-Signalling Cable for “dumb” UPSes

NOTE. YOU DO NOT HAVE THIS CABLE UNLESS YOU
BUILT IT YOURSELF. THE SIMPLE-CUSTOM CABLE IS
NOT AN APC PRODUCT.

For “dumb” UPSes using voltage signalling, if you are going to build your
own cable, we recommend to make the cable designed by the apcupsd team
as follows:

SIMPLE-CUSTOM CABLE

Signal Computer

UPS

DB9F

4.7K ohm

DB9M

DTR

4

--[####]--*

DTR set to +5V by Apcupsd

|

CTS

8

----------*---------

5

Low Battery

GND

5

--------------------

4

Ground

DCD

1

--------------------

2

On Battery

RTS

7

--------------------

1

Kill UPS Power

List of components one needs to make the Simple cable:

1. One (1) male DB9 connector, use solder type connector only.

2. One (1) female DB9/25F connector, use solder type connector only.

3. One (1) 4.7K ohm 1/4 watt 5% resistor.

4. resin core solder.

5. three (3) to five (5) feet of 22AWG multi-stranded four or more con-

ductor cable.

1. Solder the resistor into pin 4 of the female DB9 connector.

2. Next bend the resistor so that it connects to pin 8 of the female DB9

connector.

3. Pin 8 on the female connector is also wired to pin 5 on the male DB9

connector. Solder both ends.

4. Solder the other pins, pin 5 on the female DB9 to pin 4 on the male

connector; pin 1 on the female connector to pin 2 on the male connec-
tor; and pin 7 on the female connector to pin 1 on the male connector.

139