Register 1, Register 2, Register 3 – APC UPS control system User Manual

Page 196: Register 1 layout, Register 2 layout, Register 3 layout

background image

Register 1

All bits are valid on the Matrix UPS. SmartUPS models only support bits
6 and 7. Other models do not respond.

Bit

Hex
Bit

Meaning

0

0x01

In wakeup mode (typically lasts < 2s)

1

0x02

In bypass mode due to internal fault - see register 2 or 3

2

0x04

Going to bypass mode due to command

3

0x08

In bypass mode due to command

4

0x10

Returning from bypass mode

5

0x20

In bypass mode due to manual bypass control

6

0x40

Ready to power load on user command

7

0x80

Ready to power load on user command or return of line power

Register 2

Matrix UPS models report bits 0-5. SmartUPS models only support bits 4
and 6. SmartUPS v/s and BackUPS Pro report bits 4, 6, 7. Unused bits
are set to 0. Other models do not respond.

Bit

Meaning

0

Fan failure in electronics, UPS in bypass

1

Fan failure in isolation unit

2

Bypass supply failure

3

Output voltage select failure, UPS in bypass

4

DC imbalance, UPS in bypass

5

Command sent to stop bypass with no battery connected - UPS still in
bypass

6

Relay fault in SmartTrim or SmartBoost

7

Bad output voltage

Register 3

All bits are valid on the Matrix UPS and 3rd generation SmartUPS models.
SmartUPS v/s and BackUPS Pro models report bits 0-5. All others report
0-4. State change of bits 1,2,5,6,7 are reported asynchronously with ? and

195