APC UPS control system User Manual
Page 199

It looks bizarre and ugly, but is easily parsed. The # is some kind of
marker/ident character. Skip it. The rest fits this form:
• Command character - use this to select the value
• Locale - use ’b’ to find out what yours is (the last character), ’4’ applies
to all
• Number of choices - ’4’ means there are 4 possibilities coming up
• Choice length - ’3’ means they are all 3 chars long
Matrix-UPS models have ## between each grouping for some reason.
Here is an example broken out to be more readable:
CMD DFO RSP FSZ FVL
u
D
4
3
127 130 133 136
u
M
4
3
229 234 239 224
u
A
4
3
108 110 112 114
u
I
4
3
253 257 261 265
l
D
4
3
106 103 100 097
l
M
4
3
177 172 168 182
l
A
4
3
092 090 088 086
l
I
4
3
208 204 200 196
e
4
4
2
00
15
50
90
o
D
1
3
115
o
J
1
3
100
o
I
1
3
230 240 220 225
o
M
1
3
208
s
4
4
1
H
M
L
L
q
4
4
2
02
05
07
10
p
4
4
3
020 180 300 600
k
4
4
1
0
T
L
N
r
4
4
3
000 060 180 300
E
4
4
3
336 168
ON OFF
CMD == UPSlink Command.
u = upper transfer voltage
l = lower transfer voltage
e = return threshold
o = output voltage
s = sensitivity
p = shutdown grace delay
q = low battery warning
k = alarm delay
r = wakeup delay
E = self test interval
198