APC UPS control system User Manual

Page 193

background image

7

Dip switch positions (if applica-
ble)

See below

8

Register #3

See below

9

Line quality

“FF” acceptable, “00” unaccept-
able

>

Number of external battery packs
attached

SmartCell models: “nnn” where
nnn is how many external packs
are

connected

Non-SmartCell

units: whatever has been set with
>

+ and >- by the user

Matrix
UPS
(and
pos-
sibly
Sym-
metra)
specific
com-
mands
ˆ

Run in bypass mode

If online, “BYP” is received as by-
pass mode starts If already in by-
pass, “INV” is received and UPS
goes online “ERR” received if UPS
is unable to transfer

<

Number of bad battery packs

“nnn” - count of bad packs con-

nected to the UPS

/

Load current

“nn.nn” - true RMS load current
drawn by UPS

\

Apparent load power

“nnn.nn” - output load as percent-
age of full rated load in VA.

ˆV

Output

voltage

selection

(ed-

itable)

“A” - automatic according to in-
put tap, “M” - 208 VAC, “I” - 240
VAC

ˆL

Front panel language

“E” - English, “F” - French, “G”
- German, “S” - Spanish, “1” “2”
“3” “4” - ?

w

Run time conservation

“NO” (disabled) or “02” “05”
“08” - minutes of runtime to
leave in battery (UPS shuts down
“early”)

192