APC UPS control system User Manual
Page 193

7
Dip switch positions (if applica-
ble)
See below
8
Register #3
See below
9
Line quality
“FF” acceptable, “00” unaccept-
able
>
Number of external battery packs
attached
SmartCell models: “nnn” where
nnn is how many external packs
are
connected
Non-SmartCell
units: whatever has been set with
>
+ and >- by the user
Matrix
UPS
(and
pos-
sibly
Sym-
metra)
specific
com-
mands
ˆ
Run in bypass mode
If online, “BYP” is received as by-
pass mode starts If already in by-
pass, “INV” is received and UPS
goes online “ERR” received if UPS
is unable to transfer
<
Number of bad battery packs
“nnn” - count of bad packs con-
nected to the UPS
/
Load current
“nn.nn” - true RMS load current
drawn by UPS
\
Apparent load power
“nnn.nn” - output load as percent-
age of full rated load in VA.
ˆV
Output
voltage
selection
(ed-
itable)
“A” - automatic according to in-
put tap, “M” - 208 VAC, “I” - 240
VAC
ˆL
Front panel language
“E” - English, “F” - French, “G”
- German, “S” - Spanish, “1” “2”
“3” “4” - ?
w
Run time conservation
“NO” (disabled) or “02” “05”
“08” - minutes of runtime to
leave in battery (UPS shuts down
“early”)
192