beautypg.com

Red Lion IAMS User Manual

Page 19

background image

18

password protection: Programming access can be blocked by assigning a

password. The password is saved in the device in order to ensure a high
degree of protection against unauthorised modifications to the setup. Default
password 2008 allows access to all setup modules.

Signal and sensor error info via pgMMoD00

Sensor error (see limits in the table) is displayed as SE.BR (sensor break) or

SE.SH (sensor short). Signals outside the selected range (not sensor error,
see table for limits) are displayed as IN.LO indicating low input signal or
IN.HI indicating high input signal. The error indication is displayed in line 3
as text and at the same time the backlight flashes. Line 4 of the display is a
status line which displays status of relay 1 and relay 2, COM (flashing bullet)
indicating correct functioning of PGMMOD00 and arrow up/down which
indicates tendency readout of the input signal. If the figure 1 or figure 2
flashes, the unit has detected that the setpoint has been exceeded and that
the relay is in “delay” mode. When the delay time has passed and the relay
makes/breakes, the relay sign either displays or disappears.

Signal and sensor error indication without display front

Status of the unit can also be read from the red/green LED in the front of the device.

Green flashing LED 13 Hz indicates normal operation.
Green flashing LED 1 Hz indicates sensor error.
Steady red LED indicates internal error.

relay functions

5 different settings of relay function can be selected.

Setpoint:

The unit works as a single trip amplifier

Window: The relay has a window that is defined by a low and a high

setpoint. On both sides of the window the relay has the

same status.

error function:

The relay is activated by sensor error.

power: The relay is activated as long as the power is on.
off:

The relay is deactivated.