Sensor error detection limits
error indications
Sensor error detection (SE.BR, SE.SH):
Input
Range
Readout
Limit
CURR
Loop break (4..20 mA)
SE.BR
<= 3.6 mA; > = 21 mA
POTM
All, SE.BR on all 3wire
SE.BR
> ca. 126 k
Ω
LIN.R
0...800
Ω
SE.BR
> ca. 875
Ω
0...10 k
Ω
SE.BR
> ca. 11 k
Ω
TEMP
TC
SE.BR
> ca. 750 k
Ω
/ (1.25 V)
RTD, 2, 3, and 4wire
No SE.SH for Pt10, Pt20 and Pt50
SE.BR
> ca. 15 k
Ω
SE.SH
< ca. 15
Ω
Display readout below min. / above max. (1999, 9999):
Input
Range
Readout
Limit
All
All
1999
Display readout <1999
9999
Display readout >9999
Readout at hardware error
Error search
Readout
Error cause
Test of internal CJC sensor
CJ.ER
CJC sensor defect or tem
perature outside range
Checksum test of the setup in FLASH
FL.ER
Error in FLASH
Check measurement of analogue output current
AO.ER
1) Incorrect current output
(only S4...20/S20...4 mA)
Communications test PGMMOD00 / device
NO.CO
Connection error
Check that input signal matches input setup
IN.ER
1) Error levels on input
Check that saved setup in PGMMOD00 matches device
TY.ER
Setup mismatch
! Error indications in the display flash once per second. The help text explains the error.
1) The error is reset by switching off and then switching on the supply voltage to the device.