Current output:
Signal range (span) ...................................... 0...20 mA

Programmable signal ranges ...................... 0...20 / 4...20 /

20...0 and 20...4 mA

Load (max.) .................................................. 20 mA / 800

Ω / 16 VDC

Load stability ...............................................

≤ 0.01% of span / 100 Ω

Sensor error detection ................................ 0 / 3.5 / 23 mA / none

NAMUR NE 43 Upscale / Downscale ......... 23 mA / 3.5 mA

Output limitation:

on 4...20 and 20...4 mA signals .............. 3.8...20.5 mA

on 0...20 and 20...0 mA signals .............. 0...20.5 mA

Current limit .................................................

≤ 28 mA

Voltage output:
Signal range ................................................ 0...10 VDC

Programmable signal ranges ...................... 0...1 / 0.2...1 / 0...10 / 0...5 /

1...5 / 2...10 / 1...0 / 1...0.2 / 5...0 /

5...1 / 10...0 og 10...2 V

Load (min.) ................................................... 500 k

Ω

relay outputs:
Relay functions ............................................ Setpoint, Window, Sensor error,

Power and Off

Hysteresis .................................................... 0.1...25% of span or display range

On and Off delay ......................................... 0...3600 s

Sensor error detection ................................ Break / Make / Hold

Max. voltage ................................................ 250 VRMS

Max. current ................................................ 2 A / AC or 1 A / DC

Max. AC power ........................................... 500 VA
ex / I.S. approval:
FM, applicable in ......................................... Class I, Div. 2, Group A, B, C, D

Class I, Div. 2, Group IIC

Zone 2

Max. ambient temperature for T5 ............... 60°C
observed authority requirements:

Standard:

EMC 2004/108/EC

Emission and immunity ...................... EN 61326­1

LVD 2006/95/EC .......................................... EN 61010­1

FM ............................................................... 3600, 3611, 3810 and ISA 82.02.01

UL, Standard for Safety .............................. UL 508

of span = of the currently selected measurement range