Red Lion IAMS User Manual
Page 13
12
Current output:
Signal range (span) ...................................... 0...20 mA
Programmable signal ranges ...................... 0...20 / 4...20 /
20...0 and 20...4 mA
Load (max.) .................................................. 20 mA / 800
Ω / 16 VDC
Load stability ...............................................
≤ 0.01% of span / 100 Ω
Sensor error detection ................................ 0 / 3.5 / 23 mA / none
NAMUR NE 43 Upscale / Downscale ......... 23 mA / 3.5 mA
Output limitation:
on 4...20 and 20...4 mA signals .............. 3.8...20.5 mA
on 0...20 and 20...0 mA signals .............. 0...20.5 mA
Current limit .................................................
≤ 28 mA
Voltage output:
Signal range ................................................ 0...10 VDC
Programmable signal ranges ...................... 0...1 / 0.2...1 / 0...10 / 0...5 /
1...5 / 2...10 / 1...0 / 1...0.2 / 5...0 /
5...1 / 10...0 og 10...2 V
Load (min.) ................................................... 500 k
Ω
relay outputs:
Relay functions ............................................ Setpoint, Window, Sensor error,
Power and Off
Hysteresis .................................................... 0.1...25% of span or display range
On and Off delay ......................................... 0...3600 s
Sensor error detection ................................ Break / Make / Hold
Max. voltage ................................................ 250 VRMS
Max. current ................................................ 2 A / AC or 1 A / DC
Max. AC power ........................................... 500 VA
ex / I.S. approval:
FM, applicable in ......................................... Class I, Div. 2, Group A, B, C, D
Class I, Div. 2, Group IIC
Zone 2
Max. ambient temperature for T5 ............... 60°C
observed authority requirements:
Standard:
EMC 2004/108/EC
Emission and immunity ...................... EN 613261
LVD 2006/95/EC .......................................... EN 610101
FM ............................................................... 3600, 3611, 3810 and ISA 82.02.01
UL, Standard for Safety .............................. UL 508
of span = of the currently selected measurement range