11
Cable resistance per wire (max.), RTD ........ 50
Ω
Sensor current, RTD .................................... Nom. 0.2 mA
Effect of sensor cable resistance
(3 / 4wire), RTD ......................................... < 0.002
Ω / Ω
Sensor error detection, RTD ....................... Yes
Short circuit detection, RTD ........................ < 15
Ω
tC input:
Cold junction compensation (CJC)
via internally mounted sensor ................. < ±1,0 °C
Sensor error detection, all TC types ........... Yes
Sensor error current:
when detecting ....................................... Nom. 2 μA
else .......................................................... 0 μA
Current input:
Measurement range .................................... 0...20 mA
Programmable measurement ranges .......... 0...20 and 4...20 mA
Input resistance ........................................... Nom. 20
Ω + PTC 50 Ω
Sensor error detection:
Loop break 4...20 mA.............................. Yes
Voltage input:
Measurement range .................................... 0...12 VDC
Programmable measurement ranges .......... 0...1 / 0.2...1 / 0...5 / 1...5 /
0...10 and 2...10 VDC
Input resistance ........................................... Nom. 10 M
Ω
Type
Min.
value
Max.
value
Standard
B
E
J
K
L
N
R
S
T
U
W3
W5
LR
0°C
100°C
100°C
180°C
200°C
180°C
50°C
50°C
200°C
200°C
0°C
0°C
200°C
+1820°C
+1000°C
+1200°C
+1372°C
+900°C
+1300°C
+1760°C
+1760°C
+400°C
+600°C
+2300°C
+2300°C
+800°C
IEC 605841
IEC 605841
IEC 605841
IEC 605841
DIN 43710
IEC 605841
IEC 605841
IEC 605841
IEC 605841
DIN 43710
ASTM E98890
ASTM E98890
GOST 304484