beautypg.com

Red Lion IAMS User Manual

Page 12

background image

11

Cable resistance per wire (max.), RTD ........ 50

Ω

Sensor current, RTD .................................... Nom. 0.2 mA

Effect of sensor cable resistance

(3­ / 4­wire), RTD ......................................... < 0.002

Ω / Ω

Sensor error detection, RTD ....................... Yes

Short circuit detection, RTD ........................ < 15

Ω

tC input:

Cold junction compensation (CJC)

via internally mounted sensor ................. < ±1,0 °C

Sensor error detection, all TC types ........... Yes

Sensor error current:

when detecting ....................................... Nom. 2 μA

else .......................................................... 0 μA
Current input:
Measurement range .................................... 0...20 mA

Programmable measurement ranges .......... 0...20 and 4...20 mA

Input resistance ........................................... Nom. 20

Ω + PTC 50 Ω

Sensor error detection:

Loop break 4...20 mA.............................. Yes
Voltage input:
Measurement range .................................... 0...12 VDC

Programmable measurement ranges .......... 0...1 / 0.2...1 / 0...5 / 1...5 /

0...10 and 2...10 VDC

Input resistance ........................................... Nom. 10 M

Ω

Type

Min.

value

Max.

value

Standard

B

E

J

K

L

N

R

S

T

U

W3

W5

LR

0°C

­100°C

­100°C

­180°C

­200°C

­180°C

­50°C

­50°C

­200°C

­200°C

0°C

0°C

­200°C

+1820°C

+1000°C

+1200°C

+1372°C

+900°C

+1300°C

+1760°C

+1760°C

+400°C

+600°C

+2300°C

+2300°C

+800°C

IEC 60584­1

IEC 60584­1

IEC 60584­1

IEC 60584­1

DIN 43710

IEC 60584­1

IEC 60584­1

IEC 60584­1

IEC 60584­1

DIN 43710

ASTM E988­90

ASTM E988­90

GOST 3044­84