Appendix A _________________________________________________________ Modbus Reference

VAISALA ________________________________________________________________________ 61

Modbus Register Map

Table 21

Modbus Register Map

Logical

Address

(decimal)

PDU Address

(hexadecimal)

Register Description

Data

Format

Register

Type

Notes

5

00 04

T

(measured)

LSW

MSW

32-bit

float

read-only

°C

6

00 05

7

00 06

T

d/f

(measured)

LSW

MSW

32-bit

float

read-only

°C

8

00 07

11

00 0A

T

d/f

(atm)

(measured)

LSW

MSW

32-bit

float

read-only

°C

12

00 0B

21

00 14

H

2

O (measured)

LSW

MSW

32-bit

float

read-only

ppm

v

22

00 15

45

00 2C

P (measured)

LSW

MSW

32-bit

float

read-only

bara

46

00 2D

47

00 2E

ρ (measured)

LSW

MSW

32-bit

float

read-only

kg/m

3

48

00 2F

49

00 30

P

norm

(measured)

LSW

MSW

32-bit

float

read-only

bara

50

00 31

513

02 00

Fault status

16-bit

boolean

read-only

1 = no errors

514

02 01

Online status

16-bit

boolean

read-only

1 = online data

available

516

02 03

Error code

LSW

MSW

32-bit bit

field

read-only

0 = no errors

517

02 04

775

03 06

Molar mass of other

gas (set value)

LSW

MSW

32-bit

float

read/write

kg/mol

776

03 07

781

03 0C

Gas mixing ratio

(set value)

LSW

MSW

32-bit

float

read/write

0 …100 % of

SF

6

782

03 0D

783

03 0E

Pressure

normalization

temperature (set

value)

LSW

MSW

32-bit

float

read/write

-100 … 100°C

784

03 0F

1283

05 02

Automatic purge on/off*

16-bit

boolean

read/write

1= automatic

purge on

1284

05 03

Start-up purge on/off*

16-bit

boolean

read/write

1 = start-up

purge on

1285

05 04

Purge in progress*

16-bit

boolean

read/write 1 = purge in

progress, write

1 for manual

start

1537

06 00

Address

16-bit

integer

read/write

1…255 (1 …

247 allowed in

Modbus)

*Device specifications are valid only if purge functions are kept enabled. Do not modify registers 1283, 1284,

and 1285. Regular purge is needed to guarantee accurate measurements. Modify only if instructed to by Vaisala.

PDU address

Actual address bytes used in a Modbus Protocol data unit

LSW

Least significant word (bits 15 … 0)

MSW

Most significant word (bits 31 … 16)

16-bit integer

Numeric value in range 0 … 65535

16-bit boolean

Numeric value, 0 or 1

32-bit bit field

32 individual values, each 0 or 1

32-bit float

Floating point, IEEE 754 format

read-only

Register value cannot be changed with Modbus functions

read/write

Register value can be changed with Modbus functions