Vaisala DMT152 User Manual
Page 40
User's Guide _______________________________________________________________________
38 ___________________________________________________________________ M210865EN-F
AMODE [c1 c2]
where
c1 =
Channel 1 analog output mode. Available options are:
1 = 0 ... 20 mA
2 = 4 ... 20 mA
4 = 0 ... 5 V
5 = 0 ... 10 V
7 = I alarm (ON/OFF output using current)
8 = U alarm (ON/OFF output using voltage)
Modes 1 ...5 are normal measurement modes, where
malfunction alarm is always enabled, and limit alarm and
purge status alarm are disabled.
c2 =
Channel 2 analog output mode. Available options are:
1 = 0 ... 20 mA
2 = 4 ... 20 mA
4 = 0 ... 5 V
5 = 0 ... 10 V
6 = LED alarm
7 = I alarm (ON/OFF output using current)
8 = U alarm (ON/OFF output using voltage)
Enable mode 6 for channel 2 if you are using the Vaisala
LED cable.
Example:
amode 2 1
Ch1 output : 4 ... 20 mA
Ch2 output : 0 ... 20 mA