Chapter 3 _______________________________________________________________ Installation
VAISALA_______________________________________________________________________ 37
Maximum Cable Resistance Calculation for the
Barrier (Vaisala Order Code: 210664)
Calculation of the maximum cable length from barrier to transmitter:
General specifications of HMT360:
Supply voltage
U
in
= 24 V (12 ... 35 V)
Maximum current
I
out
= 20 mA
Minimum operating voltage for
HMT360
U
min
= 12 V (15 V with serial port)
Stahl 9001/51-280-091-141 (values taken from the specifications):
Rated operating voltage
U
N
= 20 ... 35 V
Transmitter supply voltage
U
S
= U
N
- 9.5 V, when
U
N
≤ 23.5 V
or U
S
= 14 V, when U
N
≥ 23.5 V
Maximum load
R
L
≤ 350 Ω
Cable resistance (as an example) R
cable
= 0.085 Ω/m/core (2 ×
0.085 Ω/m/pair)
- Calibration of Digital Transmitters with HMI41 (36 pages)
- Calibration of Series HMDW2030 and HMP130 Transmitter with HMI41 (14 pages)
- Calibration of Series HMDW6070 and HMP140 Transmitter with HMI41 (30 pages)
- HM34 (30 pages)
- HM40 (47 pages)
- HM44 (52 pages)
- HM70 (83 pages)
- HMD40 (1 page)
- HMD60 (4 pages)
- HMD70 (18 pages)
- HMDW110 (62 pages)
- HMDW80 (51 pages)
- HMI41 (74 pages)
- HMP41 (72 pages)
- HMK15 (39 pages)
- HMM100 (71 pages)
- HMM105 (23 pages)
- HMM211 (42 pages)
- HMM212 (36 pages)
- HMM213 (52 pages)
- HMP140 (28 pages)
- HMP155 (84 pages)
- HMP228 (115 pages)
- HMP230 (163 pages)
- HMP240 (130 pages)
- HMP260 (118 pages)
- HMP60 (71 pages)
- HMT100 (52 pages)
- HMT120 (87 pages)
- HMT130 (95 pages)
- HMT140 (76 pages)
- HMT310 (88 pages)
- HMT310 (105 pages)
- HMT330 (209 pages)
- HMT360 (63 pages)
- HMT360N (110 pages)
- HMW40 (1 page)
- HMW90 (110 pages)
- SHM40 (68 pages)
- RDP100 (14 pages)