Connection to a 24 VAC supply
The HMP240 transmitter can also be connected to a 24 VAC supply without
an external rectifier. However, when more than one transmitter is connected to
one 24 VAC transformer, a common loop is formed and there is an increased
risk of a short-circuit. To avoid this, always use separate floating supply for
each transmitter (see Figure 3.7 A). However, if several transmitters have to
share one transformer, the phase (
∼
) must always be connected to + connector
in each transmitter (see Figure Figure 3.7 B).
24 VAC
HMP243 transmitter
HMP243 transmitter
Controller
shared
common line