81
FX Model
Typical DC
AMPS
NEC AMPS
1-3’ one way
3-5’ one way
5-10’ one way
GTFX2524LA
104
130
2/0
2/0
2/0
GTFX3048LA
63
78
1/0
1/0
1/0
GVFX3524LA
146
182
4/0
4/0
4/0
GVFX3648LA
75
94
1/0
1/0
1/0
MAINTENANCE
If damaged or malfunctioning, the FX should be repaired by a qualified user, installer, or service center
following OutBack Power Systems’ instructions and guidelines. Please contact your energy dealer for
assistance. Incorrect repairs and/or reassembly risks malfunction, electric shock or fire.
For routine, user-approved maintenance:
• Disconnect all circuit breakers and related electrical connections before doing any cleaning or
adjustments.
• Solar modules may produce hazardous voltages when exposed to light; cover them with opaque
material before servicing any connected equipment or service at night.
• If a remote or automatic generator start system is used, disable the automatic starting circuit and/or
disconnect the generator from its starting battery while servicing. This will prevent accidental it to
starting or operation.
Recommended Wire Sizes by Length