81

FX Model

Typical DC
AMPS

NEC AMPS

1-3’ one way

3-5’ one way

5-10’ one way

GTFX2524LA

104

130

2/0

2/0

2/0

GTFX3048LA

63

78

1/0

1/0

1/0

GVFX3524LA

146

182

4/0

4/0

4/0

GVFX3648LA

75

94

1/0

1/0

1/0

MAINTENANCE

If damaged or malfunctioning, the FX should be repaired by a qualified user, installer, or service center
following OutBack Power Systems’ instructions and guidelines. Please contact your energy dealer for
assistance. Incorrect repairs and/or reassembly risks malfunction, electric shock or fire.

For routine, user-approved maintenance:
• Disconnect all circuit breakers and related electrical connections before doing any cleaning or

adjustments.

• Solar modules may produce hazardous voltages when exposed to light; cover them with opaque

material before servicing any connected equipment or service at night.

• If a remote or automatic generator start system is used, disable the automatic starting circuit and/or

disconnect the generator from its starting battery while servicing. This will prevent accidental it to
starting or operation.

Recommended Wire Sizes by Length