beautypg.com

Voltage, current and freqency ranges – Outback Power Systems GVFX Series Inverter/Charger Installation Manual User Manual

Page 78

background image

76

Single Phase

127 VAC at 60 Hz

Series Stacked

127 VAC at 60 Hz per AC output leg / 254 VAC at 60 Hz between the AC output legs

Three Phase Stacked 127 VAC at 60 Hz per AC output leg (limit three) / 220 VAC at 60 Hz between AC output legs

RECOMMENDED FX DC VOLTAGE RANGE

Note:

The last two digits in the model number designate the nominal DC voltage.

Example: GVFX3648LA =48V DC Voltage.

24V Systems

22 – 32 VDC (VDC = volts DC)

48V Systems

44 – 64 VDC

MAXIMUM DC INPUT CURRENT

Note:

This is the maximum DC current the FX will draw from the battery when starting very large AC loads.

It is not used for sizing the DC disconnect or selecting DC cable gauge. It is used to select the minimum

reasonable battery capacity.

24V FXs

300 ADC per FX (ADC = amps DC)

48V FXs

150 ADC per FX

Note:

This is the maximum continuous DC current that the FX will draw from the batteries when inverting.

GTFX2524LA

125 ADC (ADC = Amps DC)

GTFX3048LA

75 ADC

GVFX3524LA

175 ADC

GVFX3648LA

90 ADC

AC INPUT OPERATING VOLTAGE RANGE

Note:

If the AC input source is out of the range noted below, the FX will not connect or stay connected.

All LA Series Inverter/Chargers

100 – 140 VAC (VAC = volts AC)

AC INPUT FREQUENCY RANGE

Note: If the AC input source is out of the range noted below, the FX will not connect or stay connected.

All LA Series Inverter/Chargers

58 - 62 Hz

VOLTAGE, CURRENT AND FREQENCY RANGES

SPECIFIED AC OUTPUT VOLTAGE OF AN LA SERIES GRID-INTERACTIVE SYSTEM

RATED DC INPUT CURRENT

This manual is related to the following products: