Outback Power Systems GVFX Series Inverter/Charger Installation Manual User Manual
Page 81
79
12 VDC System
DEFAULT
MINIMUM
MAXIMUM
Float Voltage
13.6 VDC
12 VDC
15 VDC
Absorb Voltage
14.4 VDC
13 VDC
16 VDC
EQ Voltage
14.6 VDC
14 VDC
17 VDC
ReFloat
12.5 VDC
12 VDC
13 VDC
LBCO
10.5 VDC
9 VDC
12 VDC
LBCI
12.5 VDC
10 VDC
14 VDC
Sell RE
13 VDC
10 VDC
15 VDC
Gen Alert
Off Set Point
14 VDC
12 VDC
18 VDC
On Set Point
11 VDC
10 VDC
14 VDC
Load Shed Off Set Point
11 VDC
10 VDC
14 VDC
Vent Fan ON Set Point
13 VDC
10 VDC
16 VDC
Diversion ON Set Point
14.6 VDC
12 VDC
16 VDC
Absorb Time
1.0 hours
0.0 hours
24.0 hours
EQ Time
1.0 hours
0.0 hours
24.0 hours
Float Time
1.0 hours
0.0 hours
24.0 hours
AC2/Gen Transfer Delay
(Cycles for AC)
10 cycles
0 cycles
240 cycles
Search
6
0
50
Grid Lower Limit
114 VAC
100 VAC
120 VAC
Grid Upper Limit
140 VAC
130 VAC
140 VAC
Charger OFF/AUTO/ON
AUTO
AUX Output Option
COOL FAN
Gen Alert ON Delay
4 min
0 min
240 min
Gen Alert OFF Delay
9 min
0 min
240 min
Vent Fan OFF Delay
5 min
0 min
30 min
Gen Window Lower Limit
114 VAC
100 VAC
120 VAC
Gen Upper Window Limit
140 VAC
130 VAC
150 VAC
AC1/Grid Transfer Delay
10 Cycles of AC
0 Cycles of AC
240 Cycles of AC
Set AUX Control
AUTO
Search Pulses
8
2
20
Search Pulse Spacing
60 Cycles AC
4 Cycles AC
120 Cycles AC
Stacking Phase
Master
InPut Select
Grid
Charge Rates
Vented 24 & 48 VDC
18 AAC
0 AAC
20 AAC
Sealed 24 & 48 VDC
14 AAC
0 AAC
16 AAC
Grid Input Settings
Set AC Input Size
Grid-Tie
50 Amps
5 Amps
60 Amps
Gen Input Settings
Grid-Tie
30 Amps
5 Amps
60 Amps
FX Default Values (subject to change with FX upgrades)
C
or
rec
tion
F
ac
tor
•24VDC:
M
ultiply
12VDC
values
b
y
2
•48VDC:
M
ultiply
12VDC
values
b
y
4